Operation, Operation in case of fire, Warning – Lincoln Electric P709 GUARDIAN CONTROL SOLUTIONS User Manual

Page 54

Advertising
background image

B-4

OPERATION

B-4

OPERATION IN CASE OF FIRE

The fire suppression system can be activated in two
ways:

1. Automatically by heat, sparks and/or smoke detec-

tors.

2. Manually at the manual call point.

If there is a fire, the automatic sequence of events is as
follows:

• Acoustic fire alarm activation

• Fan motor is switched off

• Release of compressed air through solenoid valve

After a delay of 5 seconds:

• Sliding valves close

• Release of aerosol by Flame Guardian™ generator

After activation, the Flame Guardian™ remains active
for at least 30 minutes to prevent re-ignition of the fire.
This is to keep damage to the filter, as well as conse-
quential loss, to a minimum.

NOTE: Notify all parties involved that you will be test-

ing the fire safety system; See Maintenance
Section.

FUNCTIONAL TEST AND COMMISSION-
ING

To avoid accidental fire alarms and activation of the
Flame Guardian™ fire extinguishing generators,
always follow the following sequence for installation,
commissioning and maintenance.

1. Before starting, de-energize the Guardian™

Panel and/or electrically isolate the Flame
Guardian™ modules.

2. Make all connections to the Guardian™ Panel, with

the exception of the Flame Guardian™ modules.

3. Make all connections to the system control panel.

4. Create a temporary bridge to the terminal(s) for the

Flame Guardian™ with the End Of Line resistor-
diode to avoid fault alarm. See Wiring Diagram.

5. Apply the correct input power to the panel. When all

connections are correct, all indicator LEDs are off
and the display shows the text “System OK”. Make
sure panel is in RUN mode.

6. Test the detectors and system control panel as

instructed to make sure that the system is reacting
as expected and required. See specific Functional
Tests in Installation Section.

GUARDIAN CONTROL™ SOLUTIONS

All operative personal must be famil-
iar with the fire procedures.

-----------------------------------------------------------------------

WARNING

Ensure that all functional tests are
performed in accordance with the
manufacturers instructions and the
National Fire Protection Association
(NFPA) requirements and the state
and local authorities having jurisdic-
tion.

-----------------------------------------------------------------------

WARNING

Advertising