5 . 8

S e t u p

Wa t l o w S e r i e s F 4 S / D

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

(I/O, Set, Ch)

Parameters to Appear

Active: Always.

ç

CAUTION: Changes to
Sensor, Type, Units,
Decimals, Scales and Set
Point Limits will delete all
profiles stored in the F4’s
memory.

The tenth character of your
model number determines
your RTD base resistance.

F4_ _-_ _ _ _-_ (1 to 4) R G
for 100

F4_ _-_ _ _ _-_ (5 to 8) R G
for 500

and 1k

Input

601

[1]

611

[2]

621

[3]

r/w

J (0)

100

DIN

(11) for

100

RTD

models

500

DIN

(23) for

500

or

1k

models

4 to 20mA

(13)

If Sensor is set to

thermocouple:

J (0)

K (1)

T (2)

E (3)

N (4)

C (5)

D (6)

PT2 (7)

R (8)

S (9)

B (10)

If Sensor is set to RTD

or Wet/Dry Bulb:

100

DIN (11)

100

JIS (12)

500

DIN (23

500

JIS (24))

1k

DIN (25)

1k

JIS (26)

If Sensor is set to

Process:

4 to 20mA (13)

0 to 20mA (14)

0 to 5V (15)

1 to 5V (16)

0 to 10V (17)

0 to 50mV (18)

If Analog Input 2 Sen-

sor is set to Process

and Analog Input 2 is

selected:

•Vaisala 0 to 5V** (19)

•Vaisala 0 to 10V (20)

•Vaisala 0 to 20mA**

(21)

•Rotronics 0 to 5V***

(22)

Type

Select the lineariza-

tion table to apply

to the sensor.

Active: Always.

Input

600

[1]

610

[2]

620

[3]

r/w

Thermo-

couple (0)

Thermocouple (0)

RTD (1)

Process (2)

Wet Bulb-Dry Bulb* (3)

Off (4)

Sensor

Select the sensor.

Main > Setup > Analog Input x (1 to 3)

Analog Input x (1 to 3)

* A wet bulb at input 2 uses the input 1 value to calculate the rel-

ative humidity on channel 2. The humidify and dehumidify out-

puts (2A and 2B) are disabled when the input 1 temperature is too

low (32°F [0°C]) or too high (212°F [100°C]). The relative humidi-

ty display in the Main Page will display “RH Disabled” for a low

temperature error and “RH Disabled” for a high temperature error.

** The Series F4 provides temperature compensation for the

Vaisala HMM-30C Solid-state Humidity Sensor to calculate rela-

tive humidity on channel 2. The humidify and dehumidify out-

puts (2A and 2B) are disabled when the input 1 temperature is

too low (-40°F [-40°C]) or too high (320°F [160°C]). The relative

humidity display in the Main Page will display “RH Disabled”

for a low temperature error and “RH Disabled” for a high temper-

ature error.

*** The Series F4 provides temperature compensation for the

Rotronics Model H260 Capacitive Relative Humidity Sensor to

calculate relative humidity on channel 2. The humidify and de-

humidify outputs (2A and 2B) are disabled when the input 1

temperature is too low (-5°F [-20°C]) or too high (320°F [160°C]).

The relative humidity display in the Main Page will display “RH

Disabled” for a low temperature error and “RH Disabled” for a

high temperature error.

Setup Page Parameter Table

Modbus

Register

Range

read/write

Conditions for

Parameter

Description

(Modbus Value)

Default

[I/O, Set, Ch]

Parameters to Appear