SPECIFICATIONS
Input Signal:
4 to 20 mA DC.
Input Impedance: 460 Ω max @ 20 mA DC.
Enclosure: Aluminum, SS.
Air Supply: 35 to 116 psi (2.4 to 9 bar).
Air Connection: 1/4˝ NPT.
Gage Connection: 1/8˝ NPT.
Conduit Connection: 1/2˝ NPT.
Linearity: ±0.5% FS.
Hysteresis: ±0.5% FS.
Sensitivity: ±0.2% FS.
Repeatability: ±0.3% FS.
Air Consumption: .0004 scfm (.01 LPM) at 20 psig (1.4 bar) supply.
Flow Capacity: 2.1 scfm (60 LPM) at 20 psig (1.4 bar) supply.
Stroke: 185: 0.5 to 6 in (10 to 150 mm); 285: 0 to 90°.
Enclosure Rating: NEMA 4X (IP66).
Temperature: Operating: -22 to 185°F (-30 to 85°C).
Weight: 185: 3.3 lb (1.5 kg); 285: 6.4lb (2.9 kg).
Lever: 185: .39 to 1.57 in (10 to 40 mm); 285: NAMUR.

The Series 185 and 285 Smart Positioners control valve movements accurately
using an input signal of 4 to 20 mA from the controller. In addition, a highly efficient
microprocessing operator built into the product performs various functions such as
auto calibration, PID control, alarm and Hart

®

protocol.

Features
• LCD allows the user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during operation.
• Simple to use auto calibration.
• Easily equipped on small actuators because of its small size.
• Low air consumption reduces operating cost.
• Can be used in low voltage (8.5 V), leaving no limitation in controller.
• HART

®

communication available for configurating parameters or monitoring the

valve position.

• Analog feedback signal (4 to 20 mA).
• The adjustment of valve characteristics (linear, quick open, equal percentage)

available.

• Tight shut-close and shut-open can be set in the programming menu.
• PID parameters can easily be adjusted in the field without additional

communicator.

• Split ranges such as 4 to 12 mA, with 12 to 20 mA available.
• The positioner can manually actuate the valve or damper.
• An air filter regulator can be mounted directly to the positioner.

LCD SCREEN

SMART POSITIONER

3-27/32

[97.50]

3-1/64

[76.50]

4-7/64

[104.20]

SUPPLY
1/4 NPT

2-33/64

[64.00]

2-11/32

[59.60]

4-13/32

[111.90]

STAINLESS STEEL

4-31/64

[113.8]

STANDARD

CONDUIT ENTRY

1/2 NPT

8-31/64

[215.70]

DOUBLE

ACTION

SINGLE
ACTION

3-47/64

[95.00]

Series 185

Series 285

HART

®

is a registered trademark of Hart Communication Foundation