Changing between dip and custom configuration, Configuration of digital output models – Vaisala GMW90 User Manual

Page 23

Advertising
background image

Chapter 3 ________________________________________________________________ Installation

VAISALA ________________________________________________________________________ 21

Changing Between DIP and Custom Configuration

If you change the position of DIP switch 8, note the following:

When changing from DIP to Custom: The DIP settings that were used

when the power was last on are carried over to the custom settings at next

power up.

When changing from Custom to DIP: Current custom settings are

overwritten by the settings from the DIP switches at next power up.

Display layout and analog outputs are set to default settings:

- Channel 1 output parameter CO

2

, scaling 0 ... 2000 ppm.

- Channel 2 output parameter T, scaling -5 ... +55 °C.
- Channel 3 output parameter RH, scaling 0 ... 100 %RH (if humidity

measurement is present on the transmitter).

If you have a factory customized transmitter, this may lead to a situation

where the wiring label on the mounting base does not reflect the outputs

of the transmitter. To return the transmitter to its factory customized

settings, follow the instructions in section Reverting to Factory Settings

on page 76.

Configuration of Digital Output Models

Digital output models of the GMW90 series have the following

configuration interfaces:

- DIP switches on the component board control operating protocol,

serial line settings, and transmitter MAC address. For instructions, see

DIP Switches of Digital Output Models on page 22.

- You can set a jumper for RS-485 line termination on the component

board (120 Ω resistor). For location of the jumper, see Figure 4 on

page 17.

- Other settings are configured in software. You can change most

configuration settings through the service port. For connection

instructions and serial line commands, see Chapter 4, Operation, on

page 31.

- Some configuration actions can be done using the BACnet and

Modbus protocols. See the following appendices for protocol

implementation details:

- Appendix A, BACnet Reference, on page 83.
- Appendix B, Modbus Reference, on page 96.

Advertising