VAISALA______________________________________________________________________ 179

Example 5 (Timer Sequence)

Sequence:

-

The measurement is executed six times a minute, at 0 s, 10 s, 20 s,
and so on.

-

Statistics store each measurement, which is calculated once a
minute, one second after a full minute.

-

A report is sent once a minute, two seconds after a full minute.

All timers have the same elements:

-

Scale: 1 (absolute)

-

Type: 1 (periodic)

Timer 1, measurement:

-

Interval: 10000

-

Synchronization time: 0

Timer 2, statistics using the measurement as input:

-

Intervals: Update 10000, Calculation 60000

-

Synchronization time: 1000

Timer 3, reporting using both previous values:

-

Interval: 60000

-

Synchronization time: 2000