Notifier 411 Series User Manual
411 series, Slave digital alarm communicator transmitters, General
DN-6619:A2 • 4/13/2012 — Page 1 of 4
411 Series
Slave Digital Alarm
Communicator Transmitters
Miscellaneous
DN-6619:A2 • K-95
General
The 411 Series DACTs are compact, multifaceted, slave Digi-
tal Alarm Communicator Transmitters designed for a variety of
fire, security, and non-fire applications. The series features the
411 and 411UD, which provide three and four monitoring
channels (inputs) respectively. These slave DACTs are a solu-
tion for applications that require an existing (or new) fire alarm
control panel (FACP) to transmit system status to an off-site
monitoring facility for Central or Remote Station compliance.
Due to extremely flexible programming options, the 411 Series
slave DACTs are also ideal for monitoring non-fire and security
control panels. With fifteen selectable transmission formats
(including ADEMCO Contact ID) compatibility with virtually all
Digital Alarm Communicator Receivers (DACR) is ensured.
Programming can be accomplished on-site with a hand-held
programmer (PRO-411), or remotely (411UD only) using the
PK-411UD programming utility. This Windows®-based remote
upload/download software package permits system interroga-
tion and revision from a remote site.
Features
• Three (411) or four (411UD) monitoring channels (inputs).
• Inputs may be individually programmed to monitor the host
control panel for:
– Fire Alarm.
– Fire Trouble.
– Fire Supervisory.
– Process Monitoring.
– AC Power Loss.
– Security Alarm.
– Other (Fire and Non-Fire Events).
• Fully supervised trigger inputs require a contact closure for
activation.
• 12- or 24-VDC operation, jumper-selectable.
• Industry-first, UL recognized, “dialer-runaway” prevention
feature.
• Dual-line, rotary or touch-tone-dial DACT interfaces to pub-
lic switched telephone network (leased phone lines are not
required).
• Includes 15 reporting formats, including the popular
ADEMCO Contact ID format.
• Capable of transmitting the following DACT information, in
addition to vital system status of the host control panel:
– DACT troubles.
– Telephone line 1 and 2 voltage fault.
– Primary or Secondary Central Station communication
fault.
– System off-normal.
– 24-hour normal test.
– 24-hour abnormal test.
• Long-distance Carrier Access Code (CAC) compliant,
accepting up to 20-digit Central Station telephone numbers.
• Fully programmable transmittal codes for fire, security, pro-
cess monitoring, and others.
• Field-programmable with PRO-411 hand-held programmer.
• Programmable from remote site with optional PK-411UD
programming software (model 411UD only).
• View 411 Series status offsite in real time, with optional PK-
411UD programming software, without ever compromising
monitoring protection at the protected premises (model
411UD only).
• Programming sequence based on NOTIFIER’s popular
SFP-1024 Control/Communicators.
• Integral piezo sounder (both models) with local silence
switch (model 411UD only).
• One Form-C relay, fully programmable (model 411UD only).
• Complies with NFPA 72 (Central Station and Remote Sta-
tion [DACT only - not polarity reversal] Fire Alarm Systems).
• Surface Mount Technology (SMT).
• Extremely compact enclosure, measuring only 6.75"
(17.145 cm) W x 4.40" (11.176 cm) H x 1.05" (2.667 cm) D.
• Shares identical footprint with 911 Series for replacement
purposes.
Host Panel Compatibility
Host panels must include AC Fail Delay option to meet NFPA
Central Station Requirements. Panels with this feature include
RP-1001, RP-1002, RP-2001, RP-2002, System 500, System
5000, AFP-200, AFP-300, AFP-400, NFS-320, NFS-640,
NFS2-640, AFP1010, AM2020, NFS-3030, and NFS2-3030.
Housing
The 411 Series DACTs are fully enclosed in a compact hous-
ing measuring only 6.75" (17.145 cm) W x 4.40" (11.176 cm) H
x 1.05" (2.667 cm) D. The housing enclosure consists of an
aluminum backbox painted red with a matching cover secured
by two captive screws. The overlay includes large areas to
independently mark programming options for the three or four
channels (inputs), relay, and also includes printed terminal and
diagnostic LED designations. The overall compact size of the
enclosure permits mounting of these DACTs in virtually any
control panel’s enclosure, or alternately, adjacent to the host
control panel.
Phone Line Connections
Two modular phone connections on the 411 Series are acces-
sible with the cover in place and provide connections for two