Vollrath 219-02 User Manual

Page 11

Advertising
background image

3

SECTION 2

INTRODUCTION

2.1

SHIPMENT AND TRUST (REMOTE

MODELS)

The mix pump has been completely assembled, operated

and inspected at the factory. Upon arrival at the final

destination, the mix pump must be checked for any

damage that may have occurred during transit.

The mix pump should arrive in satisfactory condition.

THE CARRIER IS RESPONSIBLE FOR ALL DAMAGE

IN TRANSIT, WHETHER VISIBLE OR CONCEALED.

Do not pay the freight bill until you have checked the

equipment. Have the carrier note any visible damage

on the freight bill. If concealed damage and/or shortage

is found later, advise the carrier inspector within 10

days and request inspection. The customer must place

claim for damages and/or shortages in shipment with

the carrier. Stoelting, Inc. cannot make any claims

against the carrier.

2.2

NATIONAL SANITATION

FOUNDATION COMPLIANCE

REQ’S (REMOTE PUMP)

In order to comply with “National Sanitation Testing

Laboratory, Inc.” (NSF) code #6:

A. This unit (remote pump) must be installed with

a “NSF” listed refrigerated mix transfer line.

The mix transfer line must be pitched to cooler,

with no sags or low points, to allow complete

drainage. (See fig. 2.)

B. The product at the mix pump and in transfer line

must be maintained below 45°F (7.22°C)

Figure 2. Refrigerated Mix Transfer Line

Advertising