20

For proper heater operation:

The copper pressure tube at the burner vane must
be straight. See Fig.31.

Ensure the clear flexible tube is free of dust and
securely connected to the fitting at the burner and to
the fitting at the differential pressure switch. See
Figs. 32.

The air differential pressure orifices should be free of
blockages. If cleaning is required use pressurised air:

Orifices on pressure switch (See Fig.32)
-- Remove respective orifice from switch.
-- Hold up to light, if blocked clean the orifice.
-- Ensure orifices are securely pushed backed into

proper location on switch.

FIG. 31

Servicing the differential air pressure switch:

The differential pressure switch is non- adjustable. If
the switch does not make the circuit after inspection of
tubes and orifices, it must be replaced.

Do not jumper the switch. Doing so will cause lock-out
of the heater’s ignition control.

FIG. 32

AIR DIFFERENTIAL PRESSURE SWITCH,
TUBING & PRESSURE ORIFICES

COPPER PRESSURE TUBE

NUTS

ORIFICES

BLUE
GREEN

TUBE

FITTING