ENGINEERED WOOD CONSTRUCTION GUIDE

FORM NO. B360P

© 2011 APA – THE ENGINEERED WOOD ASSOCIATION

WWW.APAWOOD.ORG

45

WALL CONSTRUCTION

Building codes require that walls resist wind pressures caused by the design wind speeds, resist wall-racking forces
and provide weather protection. This section provides details on how wood structural panels can be used to meet these
fundamental requirements.

APA Sturd-I-Wall

®

The APA Sturd-I-Wall system consists of APA RATED SIDING (panel or lap) applied direct to studs or over nonstruc-
tural fiberboard, gypsum or rigid foam insulation sheathing*. Nonstructural sheathing is defined as sheathing not
recognized by building codes for meeting both bending and racking strength requirements.

TABLE 19

FASTENING APA RATED SIDING (PANEL) APPLIED DIRECT-TO-STUDS OR OVER NONSTRUCTURAL
SHEATHING

(a)(b)(c)(d)(e)

APA Rated

Panel Siding

Minimum Nail

(f)

Wall Stud

Spacing

(in. o.c.)

Panel Nail Spacing

Maximum Wind Speed (mph)

Shank

Diameter

(in.)

Penetration

in Framing

(in.)

Edges

(g)

(in. o.c.)

Intermediate

Supports

(in. o.c.)

Wind Exposure Category

B

C

D

3/8 Performance

Category

APA MDO

GENERAL

APA Rated Siding

16 oc

APA Rated Siding

24 oc

0.113

1.5

16

6

12

110

90

90

6

140

120

110

24

6

12

90

NP

NP

6

130

110

100

2.0

16

6

12

125

105

90

6

140

120

110

24

6

12

100

85

NP

6

140

120

110

(a) Table is based on wind pressures acting toward and away from

building surfaces, at 30-ft height in wall Zone 5 (corners) with

smallest effective area, per

Section 6.4.2.2 of ASCE 7-05 and

Section R301.2 of the 2009 IRC

. Stud specific gravity = 0.42.

(b) Recommendations of siding manufacturer may vary.
(c) For use as wood structural panel wall bracing, the minimum

fastener spacing of 6" o.c. at panel edges and 12" o.c. at interme-

diate supports shall be sufficient except:

(1) For braced wall section with Performance Category 3/8 panel

siding applied horizontally over studs 24" o.c., space nails

3" o.c. along panel edges.

(d) Hot-dip galvanized nails are recommended for most siding

applications, see

Siding Fasteners section on page 48

for more

information.

(e) Maximum stud spacing shall be in accordance with

Table 21A

.

(f) See

Table 5, page 14

, for nail dimensions.

(g) Supported panel joints shall occur approximately along the center-

line of framing with a minimum bearing of 1/2". Fasteners shall

be located 3/8" from panel edges. Siding installed over two or

more spans.

* Where panel siding is applied over foam sheathing, see APA publication

APA Rated Siding Panels over Rigid Foam Insulation Sheathing, Form C465.