Specifications – Vicor 4kW MegaPAC AC-DC Switchers User Manual

Page 25

Advertising
background image

UG:107

vicorpower.com

Applications Engineering: 800 927.9474

Page 25

Specifications

Input Characterisitcs

Input Voltage

3Æ 208/240 Vac, 1Æ 180-264 Vac, (47-500Hz) 260-352 Vdc

Power Factor (passive)

0.92 (3 Phase operation)

Inrush Current

30A rms @ 230 Vac

Ride Through Time

>20 ms at nominal line, full load

Power Fail

>3 ms warning

Conducted EMI (47-63 Hz) EN55022 Level A

Surge Immunity

(Common

Mode and Normal Mode)

EN 61000-4-5 Class 3
(Temporary loss of output power may occur which is self recoverable)

Dielectric Withstand

Primary to Chassis GND = 2,121 Vdc
Primary to Secondary = 4,242 Vdc
Secondary to Chassis GND = 750 Vdc

Ouput Characterisitcs

VI-200/VI-J00
Line/Load Regulation

0.2% max. from 10% to 100% load;
0.5% max. from 0% to 10% load

Maxi Line Regulation*

0.20% max to 0.30% max

Maxi Load Regulation*

0.20% max to 0.70% max

VI-200/VI-J00
Setpoint Accuracy*

1% for standard voltages; 2% for special or adjustable voltages

Maxi Setpoint Accuracy

1% for standard voltages;
2% for special, adjustable voltages and 48 Vdc outputs

Ripple and Noise

Std. outputs: 2% or 100 mV p-p max., whichever is greater, 10% min. load
VXI options: 50 mV p-p <15 Vdc; 150 mV p-p max. for >15V < 24
1% ripple for > 24V;
RAMPAC: 10mV p-p max. or 0.15% whichever is greater
UniPAC: see Vicor module specifications

Output Trim Range

10% -110% of nominal voltage Maxi modules
50% -110% of nominal voltage VI-200/VI-J00 modules
90% -110% of nominal voltage VI-200/VI-J00 modules 10-15 V

Overcurrent Trip Point

105-125% of full load capability of VI-200/VI-J00 modules
115% typical of full load capability of Maxi modules

Overvoltage Protection

ModuPACs: 115-135%

Efficiency

82% typical

Output Power
4kW MegaPAC
3 Phase MegaPAC

4,000W at 45°C (3 Phase); 1,500W at 45°C (1 Phase)
2,000W at 45°C (3 Phase); 1,200W at 45°C (1 Phase)

Environmental Characteristics

Storage Temperature

-40°C to 85°C

Operating Temperature*

-20°C to +45°C full power, -20°C to +65°C half power

Humidity

0 to 95% non-condensing

Altitude

Derate 2.6% total output power for each 1,000 ft to a maximum operating
altitude of 15,000 ft. Non-operating storage maximum altitude is 40K

Safety Approvals

cURus – UL 60950-1, CSA 60950-1
cTUVus – EN 60950-1, UL 60950-1, CSA 60950-1
CE Mark – Low Voltage Directive, 73/23/EEC amended by 93/68/EEC

Product Weights

3 Phase MegaPAC: 18.1lbs (8.21kgs) fully configured
4KW MegaPAC: 21.5lbs (9.77 kgs) fully configured

Warranty

2 years limited warranty.
See

vicorpower.com

for complete warranty statement.

Advertising
This manual is related to the following products: