Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 44

Advertising
background image

Publication 1769-UM002B-EN-P - July 2005

2-20 Installation and Wiring

Figure 2.13 1769-IF4 Wiring Single-ended Sensor/Transmitter Types

(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum

for a single input module.

(2 ) Series B and later modules provide this option.

+

V in 0 +
V/I in 0 -

I in 0 +
ANLG Com
V in 1 +
V/I in 1 -

I in 1 +
ANLG Com

V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +

V/I in 3 -
I in 3 +
ANLG Com

+24V dc

dc NEUT

+

+

+

-

+

-

Current

Transmitter

Voltage

Transmitter

Voltage

Transmitter

Signal

Signal

Ground

Ground

1769-IF4 Terminal Block

Signal

External 24V dc

Power Supply

(1)

(optional)

(2)

Sensor/

Transmitter

Supply

Advertising