6. Test for wiring correctness with continuity checks and also

for unwanted grounds with insulation resistance tester.

7. Place starter handle in OFF position making sure that the

internal mechanism of the cover will properly engage the

starter.

8. Install cover. Securely tighten all cover bolts making certain

that no cover bolts are omitted. Use only bolts supplied with

the enclosure.

9. Pour sealing compound into sealing fittings in accordance

with the instructions supplied with each of the approved

fittings and sealing compound package labels.

MAINTENANCE

1. Frequent inspection should be made. A schedule for main-

tenance check should be determined by the envi-

ronment and frequency of use. It is recommended that it

should be at least once a year.

2. If necessary to open enclosure for inspection or service,

always disconnect primary power source before opening

enclosure.

3. Perform visual, electrical, and mechanical checks on all

components on a regular basis.

Visually check for undue heating evidenced by

discoloration of wires or other components, damaged or

worn parts, or leakage evidenced by water or corrosion

in the interior.

Electrically check to make sure that all connections are

clean and tight, and that contacts in the components

make or break as required.

Mechanically check that all parts are properly

assembled, and operating mechanisms move freely.

CAUTION

Clean both ground-joint surfaces of body and cover before

installing. Dirt or foreign material must not accumulate on

flat ground-joint surfaces. Surfaces must seat fully against

each other to provide a proper explosionproof seal.

EMN Enclosure

NEMA

Catalog No.

Size

Poles (Phase)

Catalog Number

M-0

2 (1 Ph)
3 (3 Ph)

B100M0BX

B100M0CX

M-1

2 (1 Ph)
3 (3 Ph)

B100M1BX

B100M1CX

M-1P

2 (1 Ph)

B100MDBX

1.

Two-pole starters require on heater, three-pole starters require three heaters. These should be selected in accordance with the manufacturer's
recommendations. Most explosionproof motors are rated at 55

o

C, heaters should be selected accordingly.

Table 1

EMN24

Cutler-Hammer - B100 Series

Manaul Motor Line Starters

1