Adjusting Signal Sensitivity

Desensitizing Standard Inputs

Signal sensitivity is factory set to 25 mVrms (about 35 mV peak or 70 mV
peak-to-peak) and satisfies most applications.

Higher sensitivities can be more vulnerable to noise.

To raise sensitivity Turn the SIGNAL SENSITIVITY potentiometer (Fig.

4-12) clockwise. At full clockwise rotation, sensitivity is approximately 5 mVrms.

To lower sensitivity Turn the SIGNAL SENSITIVITY potentiometer

counterclockwise. At full counterclockwise rotation, the sensitivity is
approximately 100 mVrms.

Desensitizing Contact Closure

Jumper terminals 30 and 11 to desensitize the unit to about 1 Vrms. Signal
Sensitivity pot setting does not affect this procedure.

27

Calibrating the Speed Switch

Fig. 4-12

The

signal sensitivity
control is located
under the A DIP
switch.

Fig. 4-13

Jumper

terminals 11 to 30 to
desensitize the
SST-2000A/H for

contact closure input.