Figure 3- wiring diagram – Qmark Artisan SmartSeries®- Architectural Digital Wall Heater User Manual

Page 3

Advertising
background image

7. Insert power supply cable through cable clamp, allowing at

least 6" (152 mm) of leads to extend inside the back box.
Connect the blue lead wires of disconnect switch to the sup-
ply wire leads using wire connectors (see Figure 4, Wiring
Diagram).

NOTE: If power supply is provided by standard non-metallic
sheathed cable (Romex) and the supply voltage is 240 or 208
volts (two power wires), the white wire color must be changed
using black electrical tape to comply with the NEC. White is only
allowed for a Neutral conductor.

8. Connect building ground conductor to the back box using the

green screw located in the inside top of the back box.

9. Secure disconnect switch bracket in place by tightening

screws.

Installation of Recessed Back Box in
Existing Construction

1. Provide a wall opening 14-3/4" (375 mm) wide by 18-1/2"

(470 mm) high at the desired mounting height, but no closer
than 12" (305 mm) from floor. (See Figure 2.) Locate so at
least one side of opening is at wall stud.

2. Run a power supply cable into the knockout area in the upper

right hand corner of the wall opening (see Figure 2). All
wiring must be in accordance with National and Local
Electrical Codes. Refer to Specifications for correct wire size.

3. Remove disconnect switch bracket by loosening two screws

on the right side.

4. Install a cable clamp in the knockout in the top of the back

box.

5. Insert power supply cable through cable clamp, allowing at

least 6" (152 mm) of leads to extend inside the back box.
Connect the blue lead wires of disconnect switch to the sup-
ply wire leads using wire connectors (see Figure 4, Wiring
Diagram).

NOTE: If power supply is provided by standard non-metallic
sheathed cable (Romex) and the supply voltage is 240 or 208
volts (two power wires), the white wire color must be changed
using black electrical tape to comply with the NEC. White is only
allowed for a Neutral conductor.

6. Connect building ground conductor to the back box using the

green screw located in the inside top of the back box.

7.

Secure disconnect switch bracket in place by tightening
screws.

8. Insert back box in wall opening being careful not to damage

the supply wiring. Secure the back box in place with wood
screws or nails.

POWER SUPPLY VOLTAGE MUST BE THE SAME AS
HEATER VOLTAGE RATING SHOWN ON HEATER NAME-
PLATE. CONNECTING TO A VOLTAGE IN EXCESS OF
NAMEPLATE RATING WILL DAMAGE HEATER AND VOID
WARRANTY.
ALL CONNECTIONS MUST BE MADE WITH APPROPRIATELY
SIZED LISTED WIRE CONNECTORS.

POWER SUPPLY VOLTAGE MUST BE THE SAME AS
HEATER VOLTAGE RATING SHOWN ON HEATER NAME-
PLATE. CONNECTING TO A VOLTAGE IN EXCESS OF
NAMEPLATE RATING WILL DAMAGE HEATER AND VOID
WARRANTY.
ALL CONNECTIONS MUST BE MADE WITH APPROPRIATELY
SIZED LISTED WIRE CONNECTORS.

3

Figure 2: Locating Back Box in Existing Construction

12” Min.

(305 mm)

Nail or screw
(2 each side)

12” Min.
(305 mm)

14 1/2” Min.
(362 mm)

Disconnect switch

bracket with switch
and leads. (No discon-
nect switch on 208V
models)

Lead wires (Blue)

Power supply cable

Ground
screw

Cable
clamp

Back Box

POWER BOARD

DISCONNECT SWITCH
(PROVIDED ON ALL MODELS
EXCEPT 208V/1P UNITS)

RED JUMPER WIRE FOR
BUILDING MANAGEMENT
SYSTEM CONNECTION

OVERHEAT
THERMISTOR

REGULATING
THERMISTOR

ELEMENT

MOTOR

TRIAC

V1

G

V2

J-JUMPER

TRIAC-N

EOL
LIMIT
SWITCH

L/N

*BLU

BMS

L1

L/N

*BLK

BLK

L1

G

G1

G2

GRN

GRN

GRN

E1

R1

C

D

E

(ON GRILL)

1

3

4

2

R2

RL-4

FAN-N

HIGH

LOW

Y

E

L

W

H

T

B

L

K

TRIAC-LL

ELEMENT

Transformer

B

A

DATA CABLE

POWER
LIGHT

INFRARED
RECEIVER

OVERHEAT
LIGHT (see page 5)

DISPLAY BOARD

LEGEND
EOL

END OF LIFE SWITCH

BMS

BUILDING MANAGEMENT SYSTEM

G1, G2

GROUND SCREWS

J

JUMPER

R1, R2

MANUAL RESET RELAY

FIELD WIRING

NOTES:
1. WIRES “C”, “E” AND JUMPER “J” ARE

SUPPLIED SOLDERED TO THE PC BOARD.

2. *BLK AND *BLU LEAD WIRES ARE IDENTIFIED

WITH WHITE TAPE AT EACH STRIPPED ENDS

TO INDICATE THAT THE NEUTRAL FOR THE

120V AND 277V MODELS ARE TO BE

CONNECTED TO THESE LEADS.

B

A

J3

J1

J2

J4

ELEMENT WIRING FOR 4800W, 208V/1PH

B

A

J5

ELEMENT WIRING FOR 4800W, 240V/1PH, 277V/1PH
& 1800W 120V/1PH

Figure 3- Wiring Diagram