Wiring the ethernet port, Installing the n-l1, Surrounding space – KEYENCE N-L1 User Manual
Page 3: Installation precautions
![background image](/manuals/658123/3/background.png)
3
E N-L1-IM
•
Wiring IN1 and IN2
•
Wiring OUT1
to 4
■ Wiring the Ethernet port
Use a “straight cable” to connect the N-L1 to the hub; use a “crossover
cable” to connect it to the personal computer directly.
* Use a cable of category 5 or higher. (Both STP and UTP can be used)
* The extended length must not exceed 100 m.
■ Surrounding space
•
Install the N-L1 vertically.
When the installation direction changes,
provide adequate surrounding space so
that heat does not build up.
•
For ventilation, maintain a space of 50mm
or more from the top and bottom of the N-
L1. As long as the N-L1 is the only source
of heat generation, the N-L1 can be
installed without space on the right and
left sides.
Provide a space of 80 mm or more in front
of the N-L1 to connect the BL head.
50 mm or more on the top and bottom; no space is required on the
right and left sides
■ Installation precautions
•
When installing the N-L1, do not block the ventilation slots on the
top and bottom of the unit. Otherwise, heat builds up inside the
unit, causing product failure.
•
If the temperature of the N-L1 will foreseeable exceed the upper
limit of the operating temperature (50
°C), take the appropriate
measures such as performing forced air cooling or ensuring
proper ventilation so that the temperature does not exceed the
upper limit of the normal operating temperature (50
°C).
■ Installing and removing the N-L1 to and from the DIN
rail
•
Installing the N-L1 to the DIN rail
1
Lower the mounting tab on the back of the N-L1.
Check that the mounting tab is placed in the position shown in the
following diagram.
2
Install the N-L1 to the DIN rail as shown in the following
diagram.
Symbol
Description
Signal
direction
INCOM
Common for IN terminal
-
IN1
Used as an input terminal for the code reader.
Input
IN2
OUTCOM
Common for OUT terminal
-
OUT1
Used as an output terminal from the code reader.
Output
OUT2
OUT3
OUT4
Note
• For connection, use stranded copper wire having a
gage of AWG16 to 26 and temperature rating of 60
°C
or higher.
• The tightening torque is 0.19 N·m (1.7 lbf·in).
CAUTION
The N-L1 does not support PoE (Power over Ethernet).
Be sure to supply 24V DC power to the power terminal.
Installing the N-L1
Circuit diagram
IN1, IN2
INCOM
Internal
circuit
OUT1 to 4
OUT
COM
Load
Circuit diagram
Load
Load
Load
Load
In
te
rn
al
ci
rc
ui
t
Straight cable
Personal
computer
Crossover cable
HUB
Top
Bottom
80 mm or more
from the front
80 mm
50 mm
50 mm
Mounting tab
DIN rail
Protrusion
DIN rail
Protrusion
Mounting tab
1. Hook
2. Push
Installing the N-L1 to the DIN rail