Wiring the ethernet port, Installing the n-l1, Surrounding space – KEYENCE N-L1 User Manual

Page 3: Installation precautions

Advertising
background image

3

E N-L1-IM

Wiring IN1 and IN2

Wiring OUT1

to 4

Wiring the Ethernet port

Use a “straight cable” to connect the N-L1 to the hub; use a “crossover
cable” to connect it to the personal computer directly.

* Use a cable of category 5 or higher. (Both STP and UTP can be used)
* The extended length must not exceed 100 m.

Surrounding space

Install the N-L1 vertically.
When the installation direction changes,
provide adequate surrounding space so
that heat does not build up.

For ventilation, maintain a space of 50mm
or more from the top and bottom of the N-
L1. As long as the N-L1 is the only source
of heat generation, the N-L1 can be
installed without space on the right and
left sides.
Provide a space of 80 mm or more in front
of the N-L1 to connect the BL head.

50 mm or more on the top and bottom; no space is required on the

right and left sides

Installation precautions

When installing the N-L1, do not block the ventilation slots on the
top and bottom of the unit. Otherwise, heat builds up inside the
unit, causing product failure.

If the temperature of the N-L1 will foreseeable exceed the upper
limit of the operating temperature (50

°C), take the appropriate

measures such as performing forced air cooling or ensuring
proper ventilation so that the temperature does not exceed the
upper limit of the normal operating temperature (50

°C).

Installing and removing the N-L1 to and from the DIN

rail

Installing the N-L1 to the DIN rail

1

Lower the mounting tab on the back of the N-L1.

Check that the mounting tab is placed in the position shown in the
following diagram.

2

Install the N-L1 to the DIN rail as shown in the following
diagram.

Symbol

Description

Signal

direction

INCOM

Common for IN terminal

-

IN1

Used as an input terminal for the code reader.

Input

IN2

OUTCOM

Common for OUT terminal

-

OUT1

Used as an output terminal from the code reader.

Output

OUT2

OUT3

OUT4

Note

For connection, use stranded copper wire having a

gage of AWG16 to 26 and temperature rating of 60

°C

or higher.

The tightening torque is 0.19 N·m (1.7 lbf·in).

CAUTION

The N-L1 does not support PoE (Power over Ethernet).
Be sure to supply 24V DC power to the power terminal.

Installing the N-L1

Circuit diagram

IN1, IN2

INCOM

Internal

circuit

OUT1 to 4

OUT
COM

Load

Circuit diagram

Load

Load

Load

Load

In

te

rn

al

ci

rc

ui

t

Straight cable

Personal

computer

Crossover cable

HUB

Top

Bottom

80 mm or more
from the front

80 mm

50 mm

50 mm

Mounting tab

DIN rail

Protrusion

DIN rail

Protrusion

Mounting tab

1. Hook

2. Push

Installing the N-L1 to the DIN rail