September 2013

12

© Intek, Inc. 2013

Revision D

2.2.1 Main Electronics – contains the SCADA and HMI components

1. Transmitter(s) Power/COM: A DeviceNet 5711 cable is used all probe/sensor/4-20mA

transmitters. The color code for this cable is: RS-485 communications: white (A), blue
(B) and shield (SH); power: 24Vdc, red (+), and black (

).

2. Main Power: Power connection wires should be at least 18 AWG. Connect main power

terminals to a dedicated 120 or 240 VAC, single phase, 15-amp circuit. A main power
switch is provided near the input power terminals.

3. Network Communication (Recommended): An Ethernet connection (RJ-45 style jack) is

provided. Intek recommends using this connection for all data transmissions because:
a. More measured data is accessible through the network connection.
b. Software and calibration file updates can be done remotely.

4. Serial Communication: Connector JP3 on the CPU interface PWA (printed wiring board

#08017-1) is the RS-232 and RS-422 serial communication interface. The configuration
information for a RJ-11 to DB-9 adapter is shown in Table 1 and Figure 5.

Table 1: RJ-11 to DB-9 Module Adapter

RS-232 CONFIGURATION

RS-422 CONFIGURATION

RJ-11 Pin Out

DB-9 Pin Out

RJ-11 Pin Out

DB-9 Pin Out

1

Tx (transmit)

1

N/C

1

Tx+ (transmit+)

1

Rx- (receive-)

2

N/C

2

Tx (transmit)

2

Tx- (transmit

S)

2

Rx+ (receive+)

3

Rx (receive)

3

Rx (receive)

3

Rx+ (receive-)

3

Tx+ (transmit+)

4

N/C

4

N/C

4

Rx- (receive-)

4

N/C

5

Power (+5V)

5

Ground

5

Power (+5V)

5

Ground

6

Ground

6

Pulled high

6

Ground

6

Tx- (transmit-)

7

N/C

7

7

TBD

8

Pulled high

8

8

TBD

9

N/C

9

9

TBD

Figure 5: Serial communication interface