Leslie Controls F-1240LDW Constantemp Double Wall Low pressure steam-water Heater User Manual

Page 7

Advertising
background image

SECTION III

MAINTENANCE OF SYSTEM

COMPONENTS

Hot Water Control Valves Dismantling


























1.

Close all steam and water inlet and outlet stop
valves. Disconnect tubing from valve body and
upper diaphragm case.

2.

Disconnect Victaulic coupling (43) and remove
gasket (44). Remove reducing coupling (45) and
remove tubing (30).

3.

Loosen and remove casing bolts (5) and nuts (4).
Lift off upper diaphragm case (27).

4.

Remove retaining ring (15) from temperature
adjuster (14) followed by lock nut (13) and cover
plate (16).

5.

Take out retaining ring (12) from adjusting sleeve
(33) and take out temperature adjuster (14) and
key cylinder (10).

6.

Hold upper stem (1) fast by placing an open end
wrench on the upper stem flats and remove the
jam nut (23) with another wrench.

7.

Take out the shouldered washer (25), O-ring (24),
diaphragm (26), diaphragm plate (29), control
valve spring (3), and the spring guide washer (2)
from the lower diaphragm case (6).




8.

Take valve plug assembly from lower opening of
valve body (42).

9.

Remove socket head cap screws (7) and take off
lower diaphragm case (6). Take out O-ring (8)
from top of yoke (36).

10.

Disconnect Victaulic couplings from valve body
(42) and remove gaskets.

11.

Take out cap screws (39) and remove valve body
(42).

12.

Push temperature adjusting sleeve (33) out of
yoke (36).

13.

Valve plug assembly should not be disassembled
unless parts replacement is necessary due to wear
or damage. For disassembly, see instructions
covering assembly of valve plug and reverse
instruction procedure.

14.

All parts should be cleaned with an approved
solvent. Wipe off with a clean cloth. Do Not Use
Abrasives of any kind. Care should be taken in

F-640LDW

Steam

Pressure

psig

Inlet

Water

Temp

0

F

Set

Point

0

F

2

5

10

15

120

54

(15

0

)

60 (14

0

)

60

(13

0

)

60

(12

0

)

140

46

(36

0

)

54

(25

0

)

58

(25

0

)

60

(20

0

)

150

40

(30

0

)

49

(30

0

)

53

(27

0

)

54

(25

0

)

160

34

(30

0

)

41

(30

0

)

44

(30

0

)

46

(30

0

)


40

180

21

(30

0

)

23

(30

0

)

25

(30

0

)

28

(30

0

)

120

60

(12

0

)

60

(11

0

)

60

(10

0

)

60

(9

0

)

140

57

(15

0

)

59

(14

0

)

60

(13

0

)

60

(12

0

)

150

49

(23

0

)

54

(21

0

)

57

(18

0

)

60

(16

0

)

160

42

(30

0

)

49

(28

0

)

51

(25

0

)

56

(20

0

)

F-640LDW

Capacity and

Adjustment Table

(Capacity in GPM)

Numbers in brackets are

approximate Gain Adjustor

settings in degrees.

*Maximum water temperature

setting for F-340LDW

is 150

0

F

** Steam pressure is measured

at the Heat Exchanger inlet.


60

180

29

(30

0

)

33

(30

0

)

39

(30

0

)

44

(30

0

)

CAUTION: Do not allow valve plug assembly to fall

from lower end of the valve body.