Dvbr series direct vent gas fireplace, Hearth, Framing and finishing – Vermont Casting DVBR42 User Manual

Page 7: Gas specifications, Final finishing, Gas inlet & manifold pressures, Dvbr36 / dvbr42 certified to, High elevations, Gas line installation

Advertising
background image

7

DVBR Series Direct Vent Gas Fireplace

20000584

Cold climate installation recommendation:

When installing this unit against a non-
insulated exterior wall or chase, it is
mandatory that the outer walls be insulated
to conform to applicable insulation codes.

Hearth

A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12” (305 mm) or more from
the front of the fireplace.

Framing and Finishing

Check fireplace to make sure it is levelled
and properly positioned.

To mount the appliance:
1. Choose the location.
2. Nailing flanges are supplied with the fireplace (found

on the fireplace hearth). To level the box and secure
it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the fireplace as
shown in Figure 5.

FP549

nailing flange

1/05

Nail Top

Standoffs

Nail Side-

nailing

Flanges

FP549

Fig. 5 Nailing flanges.

Gas Specifications

Max.

Min.

Gas

Input

Input

Model

Fuel

Control

B.T.U.H

B.T.U.H.

DVBR36RN

Natural Gas

Millivolt Hi/Lo

24,000

16,000

DVBR36RP

Propane

Millivolt Hi/Lo

24,000

17,500

DVBR42RN

Natural Gas Millivolt Hi/Lo 27,000

18,000

DVBR42RP

Propane

Millivolt Hi/Lo 27,000

19,700

Final Finishing

Noncombustible materials such as brick and tile can be
extended over the black face of the unit (Do not cover
the glass door.) If a Trim Kit is to be installed, brick and
tile will have to be installed flush with the side of this
appliance.

Gas Inlet & Manifold Pressures

Natural

LP

Minimum Inlet Pressure

5.5” w.c.

11.0” w.c.

Maximum Inlet Pressure

14.0” w.c. 14.0” w.c.

Manifold Pressure

3.5” w.c. 10.0” w.c.

DVBR36 / DVBR42

Certified to

ANSI Z21.88-2002 / CSA 2.33-2002

Vented Gas Fireplace Heater

Units: GFCN3J0, F14BR0, GFCN3M0, G14BR0

High Elevations

Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).

Gas Line Installation

When purging gas line the front glass must
be removed.

The gas pipeline can be brought in through the right
side of the appliance. Knockouts are provided at con-
venient locations to allow for the gas pipe installation
and testing of any gas connection.
The gas line connection can be made with 3/8” copper
tubing, 1/2” rigid pipe or an approved flex connector.
Since some municipalities have additional local codes,
it is always best to consult your local authority and the
CSA-B149.1 installation codes. For US installations
consult the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54.

FP297A

INSTA VENT FREE

UVHB26 GAS SUPPLY

7/1/98

FP297A

Fig. 6 Typical gas supply installation.

1/2” Gas Supply

1/2” NPT X 1/2” Flare Shut-off Valve

3/8” Flex line
(from valve)