DIN Rail High-Voltage Switch

Crestron DIN-8SW8

3. When the desired Net ID is displayed, press the SETUP button to

exit the Setup mode. The SETUP LED extinguishes.

NOTE: If an invalid Net ID is set (00, 02, FF), “Er” will be
displayed on the NET ID display. The DIN-8SW8 will revert to
the previously set Net ID.

NOTE: The DIN-8SW8 will leave the Setup mode after 10
seconds of inactivity. The DIN-8SW8 will revert to the previously
set Net ID.

NOTE: A small label (with numbers and letters) is provided on
the front panel of the DIN-8SW8 to document the unit’s Net ID in
the case where power is not available. Apply a mark over the digits
that correspond to the assigned Net ID.

NET ID Label (“3C” Shown)

When setting the Net ID, consider the following:

• The Net ID of each unit must match an ID code specified in the

SIMPL™ Windows

®

program.

• Each network device must have a unique Net ID.

For more details, refer to the Crestron Toolbox help file.

Installation

The DIN-8SW8 must be installed by a licensed electrician, in accordance
with all national and local codes.

CAUTION: This equipment is for indoor use only. Mount in a well
ventilated area. The ambient temperature must be 0º to 40º C
(32º to 104º F). The relative humidity must be 10% – 90%
(non-condensing).

NOTE: When installing in an enclosure, high-voltage devices should be
grouped separately from low-voltage devices.

10

DIN Rail High-Voltage Switch: DIN-8SW8 Operations & Installation Guide – DOC. 6666B