Model 5128/29 Fire Slave Communicator Installation Manual

8

150805

3.3.4

Wiring and Board Layout Diagram

Figure 3-1 Model 5128/29 Wiring and Board Layout

3.3.5

Electrical Ratings

* Supervised for opens only. No ground fault detection is provided.

PRIMARY DC

VDC: 18 - 40

Current draw, standby at 24 VDC

143 mA max. with annunciator attached

84 mA max. without annunciator

Current draw, alarm at 24 VDC

227 mA max. with annunciator attached

154 mA max. without annunciator

AC RATING

120 VAC @ 60Hz, 45 mA max.

CHANNEL (ZONE) INPUTS*

Active High

Dry Contacts

18 - 30 VDC input

15 mA max. current draw

4.7 VDC, 6 mA max.

MAX. WATCHDOG RESPONSE

50 seconds

DC Power
(See Section 3.4)

Earth Ground

5230 Connector
(See Section 3.10.1)

Relay Terminals

Contact Rating

1A @ 24VDC or 24VAC

Silence Button
(See Section 7.2)

Channel Inputs
(See Section 3.6)

Low AC Channel
(See Section 3.7)

Direct AC Monitoring
(See Section 3.7.3)

To Telco
Lines (See
Section 3.9)

(See Section 3.8)

All Circuits Supervised
Power Limited except

Direct AC Monitoring,

which is supervised only