2 installing 4-wire class a smoke detectors, Figure 4-36 – SilentKnight 5820XL User Manual

Page 62

Advertising
background image

Model 5820XL / 5820XL-EVS Installation Manual

LS10061-001SK-E

4-29

3.

Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connected to
the odd numbered Flexput circuit.

Figure 4-36 Class B 4-Wire Smoke Detector Connections

Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to

refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.

4.12.4.2 Installing 4-Wire Class A Smoke Detectors

Figure 4-37 illustrates how to install a 4-wire Class A detectors.

Conventions used for wiring 4-wire Class A loops:

1.

Up to two Class A 4-wire loops can be connected to the control panel at once.

2.

Smoke power is supplied to each Class A loop as shown in Figure 4-37.

Figure 4-37 Class A 4-Wire Smoke Detector Connections

Air Products

PAM-2

Model 160150

Supervision

Module

ESL 449CT

Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.

Supervised
Power Limited

4.7 k

EOL

Air Products

PAM-2

Model 160150

Supervision

Module

Air Products

PAM-2

Model 160150

Supervision

Module

Supervised
Power Limited