2 installing 4-wire class a smoke detectors, Figure 4-36 – SilentKnight 5820XL User Manual
Page 62
Model 5820XL / 5820XL-EVS Installation Manual
LS10061-001SK-E
4-29
3.
Each loop gets smoke power from the even numbered Flexput circuit and the contact input is connected to
the odd numbered Flexput circuit.
Figure 4-36 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple Flexput circuits, the lowest Flexput circuit number is used to
refer to the circuit pair. For example, Figure 4-36 uses both Flexput circuit 5 and 6, so in programming it
would be referred to as point 5.
4.12.4.2 Installing 4-Wire Class A Smoke Detectors
Figure 4-37 illustrates how to install a 4-wire Class A detectors.
Conventions used for wiring 4-wire Class A loops:
1.
Up to two Class A 4-wire loops can be connected to the control panel at once.
2.
Smoke power is supplied to each Class A loop as shown in Figure 4-37.
Figure 4-37 Class A 4-Wire Smoke Detector Connections
Air Products
PAM-2
Model 160150
Supervision
Module
ESL 449CT
Note:
Flexput circuit 5 and 6
used as an example.
Any Flexput point pairing
could be used.
Supervised
Power Limited
4.7 k
EOL
Air Products
PAM-2
Model 160150
Supervision
Module
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised
Power Limited