Installation, Air for combustion and ventilation – Desa Tech S26NTA User Manual

Page 7

Advertising
background image

www.desatech.com

110361-01F

7

If the actual Btu/Hr used is less than the maximum

Btu/Hr the space can support, the space is an un-

confined space. You will need no additional fresh

air ventilation.

WARNING: If the area in

which the heater may be oper-

ated is smaller than that defined

as an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building
This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two perma-

nent openings: one within 12" of the ceiling and

one within 12" of the floor on the wall connecting

the two spaces (see options 1 and 2, Figure 2). You

can also remove door into adjoining room (see

option 3, Figure 2). Follow the National Fuel Gas

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for

Combustion and Ventilation for required size of

ventilation grills or ducts.

AIR FOR COMBUSTION

AND VENTILATION

Continued

Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or

ducts. You must provide two permanent openings:

one within 12" of the ceiling and one within 12"

of the floor. Connect these items directly to the

outdoors or spaces open to the outdoors. These

spaces include attics and crawl spaces. Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.
IMPORTANT:

Do not provide openings for inlet

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic

will activate the power vent.

Figure 3 - Ventilation Air from Outdoors

Figure 2 - Ventilation Air from Inside

Building

Outlet

Air

Ventilated

Attic

Outlet

Air

Inlet

Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills

Into Adjoining Room,

Option 2

Ventilation

Grills

Into Adjoining

Room,

Option 1

12"

12"

INSTALLATION

NOTICE: This heater is intended

for use as supplemental heat.

Use this heater along with your

primary heating system. Do not

install this heater as your pri-

mary heat source. If you have a

central heating system, you may

run system’s circulating blower

while using heater. This will help

circulate the heat throughout the

house. In the event of a power

outage, you can use this heater

as your primary heat source.

WARNING: A qualified ser-

vice person must install heater.

Follow all local codes.

Advertising