Terminal identification
Generic wiring
Viconics Part Numbers
VT7200C5x00(x)
Viconics number
VT7200F5x00(x)
Description / Application
1 or 2 Floating outputs
Description / application
1 or 2 Analog outputs
1 or 2 On/Off outputs
4- 24 V~ Hot
24 V~ Hot
4- 24 V~ Hot
24 V~ Hot
5- 0 V~ Com
24 V~ Com
5- 0 V~ Com
24 V~ Com
6- Aux BO 5
BO 5-Aux
6- Aux BO 5
BO 5-Aux
7- Aux BO 5
BO 5-Aux
7- Aux BO 5
BO 5-Aux
8- BO 3 Open Heat
BO 3
9- BO 4 Close Heat
BO 4
9- AO 2 Heat
AO 2
10- BO 1 Open Cool
BO 1
10- AO 1 Cool
AO 1
11- BO 2 Close Cool
BO 2
Not used Blank
Blank
12- BI 1
BI 1
12- BI 1
BI 1
13- RS
RS
13- RS
RS
14- Scom
Scom
14- Scom
Scom
15- BI 2
BI 2
15- BI 2
BI 2
16- UI 3 COS / COC /SS
UI 3
16- UI 3 COS / COC /SS
UI 3
Remote inputs ( All models )
BI 1
RS
Scom
BI 2
UI 3
OR
Contact
- Rem NSB
- Motion
- Window
Contact
- Door
- Remote Override
- Filter alarm
- service alarm
Remote wall sensor
- S3010W1000
- S3020W1000
SS ( supply sensor )
- S1010E1000
- S2000D1000
COS ( changeover sensor )
- S1010E1000
COC/NH
- Normally heat
- Closed contact = cold water
COC/NC
- Normally cool
- Closed contact = heat water
#4 24 V~ Hot
#5 24 V~ Com
#6
#7
#4 24 V~ Hot
#5 24 V~ Com
#6
#7
Auxiliary output ( All models )
- Dry contact to end device 24 V~ maximum
- 24 Vac power to relay
R
R