Engineering Guide Specs

Viconics Electronics Inc

VH7200 Series Digital PI Humidity Controller

June 2008

Document #028-8018-R00

Viconics VH7200 Digital PI Humidity Controller
General –
The VH7200 family is specifically designed for control of humidification and dehumidification
equipment such as steam header direct injection, desiccant wheel, or stand alone humidification /
dehumidification equipment. The VH7200 features a complete embedded humidity control solution with a backlit
LCD display. Non-communicating stand-alone as well as communicating BACnet, Echelon and Zigbee wireless
models are available depending on the application.

Quality Assurance - The humidistat shall be manufactured within a certified ISO-9001 and ISO-14001 facility
and must have the following industry approvals:

All models:

• UL 873 (US)

• CSA C22.2 No.24 (CANADA)

• File E27734 with CCN XAPX (US) and XAPX7 (CANADA)

• Industry Canada : ICES-003 (Canada)

Stand-Alone, BACnet & LON models:

• FCC Compliant to CFR 47, Part 15, Subpart B, Class A (US)

• CE EMC Directive 89/336/EEC (Europe Union)

• C-Tick AS/NZS CISPR 22 Compliant (Australia / New Zealand)

Wireless models

• FCC: Compliant to: Part 15, Subpart C

VH72xX
General –
The low-voltage humidistat shall be capable of on/off dehumidification as well as (on/off and/or
analog 0-10Vdc humidification)
. The humidistat shall be a (non-communicating stand-alone model, BACnet
MS_TP communicating model, Echelon Lontalk communicating model or Zigbee wireless communicating
model).

• Humidistat shall provide accuracy of +/-3% over control range.

• Humidistat shall be equipped with a large, 2 line, 16 character LCD dual intensity backlit display with

two status LEDs showing HUM (Humidification), DEHUM (Dehumidification).

• Humidistat shall achieve accurate relative humidity control using a unique PI proportional-integral

algorithm. Traditional differential-based humidistats are not acceptable.

• Humidistat shall have an embedded local “real text” configuration utility for simplified sequence

selection, start-up and configuration using an integrated three-button keypad. Humidistats requiring
external configuration tools or network interface for start-up and configuration are not acceptable.

• Humidistat shall have an internal relative-humidity sensor in addition to embedded humidification and

dehumidification sequences. The humidistat shall have a 0-10Vdc analog output and/or on/off output to
control modulating humidifiers. The humidistat shall also have a discreet output (dry contact) to activate
. Dessicant type or mechanical dehumidification equipment.

• Humidistat shall have an input for a remote relative humidity sensor (0-10Vdc). Remote sensor shall be

auto-sensing and require no internal configuration. While connected the internal RH sensor shall be
disabled

• Humidistat shall have ability to display the actual relative humidity directly on the LCD display.

• Humidistat shall have adjustable relative humidity setpoints as well as adjustable maximum

humidification (from 10% to 90% relative humidity) and minimum dehumidification limits (from 15%
to 95% relative humidity).

• Humidistat shall be capable of humidity set point reset based upon outdoor temperature sensing for

added flexibility (outdoor temperature sensor or network signal required). When an outdoor air
temperature sensor is connected, the humidistat shall be capable of displaying the outdoor air
temperature on the local LCD display.

• Humidistat shall have integrated proportional high-limit logic and input (0-10Vdc humidity sensor

required) for discharge humidity sensor. This feature shall prevent excess condensation in the supply
duct.Humidistat shall be capable of displaying the high limit when a humidity sensor is connected.
Humidistat shall have an adjustable “reset humidity setpoint” from 10% RH to 90% RH. The humidistat
will override the user relative humidity setpoint and revert to this setpoint when the outside air
temperature reaches the low temperature setpoint (adjustable from –40°F to 15°F (-40°C to –9.5°C))
*Models VH7270K1000x and VH7270F1000x only