Viconics C1024 User Manual

Viconics For Home

Advertising
background image

1

ELECTRONIC THERMOSTAT: C1024

FOR THERMOELECTRIC ZONE VALVES

Modulating 24 Vac pulsed output

For N.O. or N.C. valves

For heating or cooling applications

DESCRIPTION

The C1024 series thermostats are microcomputer-based,
proportional and integral (PI) devices with one 24 Vac pulsed
output ( time proportioning ). The thermostats are designed
to be used with thermoelectric valve actuators ( wax valve ).
The output modulates the amount of open time vs. close time
on an 8 minutes cycle. The thermoelectric valve is either fully
open or fully closed. The best performances are on
perimeter reheat with hydronic hot water baseboards.
The thermostats also contain one dip switch to adjust for the
following applications:
• Heating with N.C. valves

• Cooling with N.O. valves
• Heating with N.O. valves

• Cooling with N.C. valves

HOW TO ORDER

C1024

-

01 = °C & °F scale with blind cover
Internal setpoint adjustment

02 = 10 to 30 °C scale

03 = 50 to 90 °F scale

DIMENSIONS

SPECIFICATIONS

Operating Conditions:

-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing

Sensor:

Local 47 K NTC thermistor

Resolution:

± 0.1 °C ( ± 0.2 °F )

Control accuracy:

± 0.2 ° C ( ± 0.4 °F ) ( calibrated )

Ranges:

C1024-01: Blind °C & °F
C1024-02: 10 °C to 32 °C
C1024-03: 50 °F to 90 °F

Proportional band for room

temperature control:

1.8°C ( 3.2°F )

24 Vac pulsed output:

0.5 A max at 30 Vac.

Power:

24 Vac -15%, +10% 50/60 Hz; 2 VA

24 Vac PULSED OUTPUT (TIME PROPORTIONING)

This output is designed to give true PI time proportioning
modulation out of 2 position 24 Vac on/off relays or valves.
This time proportioning modulation gives a much more
precise temperature control than conventional mechanical on
/ off thermostats with anticipator. When stabilized, the
thermostats will cycle the end device ( relay or valve ) 8 times
per hour with a duty cycle that varies with demand.
The 24 Vac pulsed output controls the room temperature
using a time proportioning control algorithm on an 8 minute
time cycle.

Ex.:

PI demand

Time on

Time off

Total cycle

50 %

4 min.

4 min.

8 min.

25 %

2 min.

6 min.

8 min.

THERMOSTAT INSTALLATION

Important: Electronic controllers require special care for
wiring and startup. To avoid problems, carefully follow
the procedures below.
Be sure to have all the literature on hand for all components
installed: controller, actuators, relay, etc...

Look at the wiring diagrams, and study them carefully. Be
sure that you understand how the system is supposed to
work.

Make the wiring according to the wiring diagrams. Respect
polarity for power terminals # 3 & # 4 between multiple
controllers if the same transformer is used.

Remove security screw on left side of thermostat cover.

Open up by pulling on the bottom side of thermostat.

32 mm

( 71 mm )

2.8"

1.275"

( 83 mm )

3.275"

SECURITY SCREW

OR FROM BACK

FROM TOP

WIRING

BASE

( 114 mm )

4.5"

50

70

60

90

80

F