Locating stove continued, Minimum clearances to combustible surfaces – Vogelzang BX42E User Manual

Page 7

Advertising
background image

VGZ-005 / 20120202.0

BX42E-SN /

Page 7

Vogelzang International Corp.

CAUTION: KEEP FURNISHINGS AND OTHER
COMBUSTIBLE MATERIALS AWAY FORM THE
STOVE.

Figure 8 – Top View

Minimum Corner Clearances from

Combustible Surfaces

36"

36"

CORNER CLEARANCES

MINIMUM CLEARANCES

TO COMBUSTIBLE SURFACES

Unit to Sidewall ....................... 36 inches
Unit to Backwall ...................... 36 inches
Unit Corner to Wall .................. 36 inches
Pipe Connector to Backwall ... 38 inches
Pipe Connector to Ceiling ...... 18 inches

LOCATING STOVE continued…

sections together. DO NOT connect this stove to
any air distribution or duct system.

5. R e c h e c k c l e a r a n c e s f r o m t h e s t o v e ,

connector stove pipe, and corner clearanc-
es using the illustrations (figure 6–8) and
your local building codes or fire protection
ordinances.

NOTE: ANY WALL CONTAINING COMBUSTI-
BLE MATERIAL SUCH AS WOODEN STUDS OR
DRYWALL AND FACED WITH BRICK OR STONE
MUST BE CONSIDERED A COMBUSTIBLE
SURFACE.

6.

DO NOT INSTALL THIS STOVE IN A MOBILE
HOME, MANUFACTURED HOME, TRAILER OR
TENT – NO EXCEPTIONS! (HUD Federal Stan-
dard: 24 CFR Ch.XX)

Figure 7 – Minimum Clearance Dimensions from Combustible Surfaces

7. T h e c l e a ra n c e s p r ov i d e d a r e m i n i mu m

dimensions determined by the NFPA. Installation
of this stove must comply with the latest edition of
NFPA 211 and/or your local building code rulings.
Use whichever minimum dimensions are
LARGEST.

Clearances listed and shown MUST be adhered to
for safe operation of this appliance.

CLEARANCES

MAY NOT BE REDUCED BY ANY MEANS.

Failure to follow these minimum clear-
ance requirements may result in an unsafe
installation and could cause a fire.

8. This stove is NOT a UL listed stove.