Checks and adjustments, Gas supply pressure, Manifold gas pressure adjustment – Sears N8MPL050B12B1 User Manual

Page 27: Warning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Duct Design and Duct Installation Requirements

See Section 10.

Internal Filter in Top Return Installation

When installing top-mounted filter inside the furnace, install the fil­
ter clips on the edge of the top duct opening with the wider end of
the clips toward the blower as shown in Figure 32. Clips may be
obtained from your distributor or fabricated from sheet metal

(Figure 33). Insert filterintoside clips firstand push filter back until

it is fully engaged into back clip.

NOTE: If filters are only suitable for heating application, ad­

vise homeownerthat filter size may need to be increased if air
conditioning is added.

Addition Of Air Conditioning

See Section 10.

12. Checks and Adjustments

Startup

NOTE: Refer to startup procedures in the Users Information

Manual.

WARNING

ELECTRICAL SHOCK, FIRE, OR EXPLOSION

HAZARD.

Failure to follow safety warnings exactly could

result in death, personal injury and/or property
damage.

If any sparks, odors or unusual noises occur,

immediately shut OFF gas and power to furnace.

Check for wiring errors or obstruction to blower.

Gas Supply Pressure

Gas supply pressure should be within minimum and maximum val­
ues listed on rating plate. Pressures are usually set by gas suppli­
ers.

(See LP Gas Conversion Kit instruction manual for furnaces con­

verted to LP gas.)

Manifold Gas Pressure Adjustment

NOTE: Make adjustment to manifold pressure with burners oper­

ating^_________________________________________________

WARNING

FIRE OR EXPLOSION HAZARD.

Failure to turn OFF gas at shut off before connecting

manometer could result in death, persona! injury
and/or property damage.

Turn OFF gas at shut off before connecting

manometer.

1. With gas OFF, connect manometer to manifold pressure tap

on outlet of gas control valve. See Figure 34. Use a manome­
ter with a

0" to 12 " water column range.

2.

Turn gas ON. Operate the furnace by using ajumper wire on
the R to W thermostat connection on the control.

3.

Remove manifold pressure adjustment screw cover on fur­
nace gas control valve. Turn adjusting screw counterclock-

441 01 2613 02