Part x. troubleshooting – Austin Hughes IGM-03 User Manual

Page 76

Advertising
background image

www.austin-hughes.com

UM-IGM-03-Q314V1

P.71

Part X. Troubleshooting

3. How to move out a slave EC Box ( without a replacement ) ?

Step 1 -

Prepare an appropriate length Cat. 5 / 6 cable

Step 2 -

Disable alarm email in < Alarm > page

Step 3 -

Use the Cat. 5 / 6 cable to bridge over the removed slave EC Box to minimize log / data loss

Step 4 -

Power off and remove the slave EC Box from connection

Step 5 -

Reconfigure and reset the level for the affected slave EC Box ( es ) which next to the removed

slave EC Box

Step 6 -

Disable the removed slave EC Box in < Setup > page

Step 7 -

Enable the EC Box ( es ) in < Setup > page based on the new level setting in Step 5

Step 8 -

Click “ Apply “ to save the setting change

Step 9 -

Enable alarm email in < Alarm > page

Ignore step 1, 3, 5 and 7 if the removed slave EC Box is in the last level

4. How to add an extra slave EC Box to an existing Master IP group ?

Step 1 -

Prepare a new slave EC Box and set the slave EC Box level accordingly

( Please refer to user manual < 1.5 > for details )

Step 2 -

Prepare an appropriate length Cat. 5 / 6 cable

Step 3 -

Disable alarm email in < Alarm > page

Step 4 -

Install, connect and power on the new slave EC Box

Step 5 -

Reconfigure and reset the level for the affected slave EC Box ( es ) which next to the added

slave EC Box

Step 6 -

Enable the added slave EC Box in < Setup > page

Step 7 -

Enable the EC Box ( es ) in < Setup > page based on the new level setting in Step 5

Step 8 -

Click “ Apply “ to save the setting change

Step 9 -

Configure the new slave EC Box in < EC Box Setting > page such as Name, Location

Step 10 -

Enable alarm email in < Alarm > page

Ignore step 3, 5, 7 and 11 if the added slave EC Box is in the last level

Advertising