Appendix A: Wiring

deltamotion.com

29

Wiring Power


Voltage: +
24VDC ( 21.6 – 26.4VDC)
Current rating: Minimum 500 mA

UL and CUL Requirements

For UL and C-UL compliance, the power supply must be Class 2. Class 2
power supplies are limited to 100W output. No additional fusing is
required if a class 2 power supply is used.

RMC75E and RMC75P

RMC75S

Tighten the wire clamp screws on the terminal blocks to 7 lb-in (0.8
Nm).

RMC75E or RMC75P

Power Supply

+24 VDC

Cmn

Protective Earth

Ground

+24 Vdc PS

PS Return

Case

AC

Line

RMC75S

Power Supply

+24 VDC

Cmn

Protective Earth

Ground

Case

+24 Vdc PS

PS Return

AC

Line