Accessories, Cooling performance with extended ratings, 2ac14 split system air conditioner – Ducane BC User Manual

Page 6

Advertising
background image

2AC14 Split System Air Conditioner

14

Accessories

Description

Used with

Catalog #

Hard Start

2AC14**18, 24, 30, *42

12W19 (Factory Installed)

Hard Start

2AC14**36, *48, *60

12W20

Low Pressure Switch

All models

14W08

High Pressure Switch

All models

14W09

Low Ambient

All models

14W11

Crankcase Heater

2AC14**18, 24, 30, *42

14W04

Crankcase Heater

2AC14**36, *48, *60

14W05

Short Cycle Protection

All models

14W07

Liquid Line Solenoid

All models

20443001

Compressor Sound Blanket

2AC14**18, 24, 30, *42

14W00

Compressor Sound Blanket

2AC14**36, *48, *60

14W03

TXV Kit

2AC14**18, 24, 30, 36

A2TXV01

TXV Kit

2AC14*42, 48, 60

A2TXV02

Form No. D2AC14B,L,BC,LC-100 (10/08)

©2008 Allied Air Enterprises Inc., a Lennox International Inc. Company

Printed in the U.S.A.

www.ducanehvac.com

1-800-448-5872

All specifications and illustrations

subject to change without notice

and without incurring obligations.

Outdoor

Model

Indoor Model

Indoor

Temp

DB/WB

˚F

Outdoor Temp - DB˚F

65

82

95

105

115

Piston or

Field

Installed

TXV

Factory

Installed

TXV

Btuh

S/T

kW

Btuh

S/T

kW

Btuh

S/T

kW

Btuh

S/T

kW

Btuh

S/T

kW

2AC14**18P

E(C,H,M,U)

1P23(A,B)+TXV

E(C,H,M,U)

2T23(A,B)

1P23(A,B)+TXV

85/72

21,600

.65

1.38 20,700 .70 1.57 20,200 .72 1.65 19,200 .75 1.71 17,700 .75 1.77

80/67

20,400

.67

1.33 19,500 .72 1.51 19,000 .74 1.58 18,000 .77 1.65 16,700 .77 1.70

75/63

18,900

.72

1.28 18,000 .77 1.45 17,600 .79 1.52 16,700 .82 1.58 15,500 .83 1.64

2AC14**24P

E(C,H,M,U)

1P23(A,B)+TXV

E(C,H,M,U)

2T23N(A,B)

85/72

26,900

.70

1.66 25,700 .74 1.87 25,000 .77 1.96 23,800 .80 2.03 22,000 .80 2.09

80/67

25,400

.72

1.61 24,200 .77 1.81 23,600 .79 1.89 22,400 .82 1.96 20,800 .83 2.02

75/63

23,500

.77

1.56 22,400 .82 1.74 21,900 .84 1.82 20,800 .88 1.89 19,300 .88 1.95

2AC14**30P

E(C,H,M,U)

1P36(A,B,C)+TXV

E(C,H,M,U)

2T36N(A,B,C)

85/72

32,600

.65

2.10 31,100 .69 2.36 30,400 .71 2.47 28,800 .74 2.56 26,700 .74 2.65

80/67

30,700

.67

2.03 29,300 .71 2.28 28,800 .73 2.38 27,200 .76 2.47 25,200 .76 2.55

75/63

28,500

.71

1.96 27,200 .76 2.20 26,500 .78 2.30 25,200 .81 2.38 23,300 .82 2.46

2AC14**36P

E(C,H,M,U)

1P36(A,B,C)+TXV

E(C,H,M,U)

2T36N(A,B,C)

85/72

39,500

.64

2.53 37,600 .68 2.86 36,700 .71 2.99 34,900 .73 3.10 32,300 .74 3.20

80/67

37,200

.66

2.45 35,500 .70 2.76 34,600 .73 2.88 32,800 .75 2.99 30,500 .76 3.08

75/63

34,500

.71

2.37 32,900 .75 2.86 32,100 .76 2.78 30,500 .81 2.89 28,200 .81 2.97

2AC14*42P

E(C,H,U)

1P49NC+TXV

E(C,H,U)

2T49NC

85/72

45,600

.64

3.92 43,500 .68 3.30 42,500 .70 3.46 40,300 .73 3.59 37,400 .74 3.70

80/67

43,000

.66

3.83 41,000 .70 3.18 40,000 .73 3.33 38,000 .75 3.46 35,200 .76 3.57

75/63

39,800

.71

3.73 38,000 .75 3.07 37,100 .78 3.22 35,000 .81 3.34 32,600 .81 3.44

2AC14*48P

E(C,H,U)

1P349NC+TXV

E(C,H,U)

2T49NC

85/72

54,700

.68

3.41 52,200 .72 3.95 51,000 .75 4.18 48,400 .78 4.37 44,800 .78 3.54

80/67

51,600

.70

3.27 49,200 .75 3.79 48,000 .77 4.00 45,600 .80 4.18 42,200 .81 4.34

75/63

47,800

.75

3.13 45,600 .80 3.62 44,500 .82 3.83 42,300 .85 4.00 39,100 .86 4.15

2AC14*60P

E(C,H,U)

1P62NC+TXV

E(C,H,U)

2T62NC

85/72

61,100

.68

4.27 58,200 .73 4.82 56,800 .75 5.04 54,000 .78 5.24 50,000 .78 5.40

80/67

57,500

.86

4.02 54,800 .75 4.65 53,500 .77 4.86 50,800 .80 5.05 47,100 .81 5.20

75/63

51,800

.84

3.92 50,800 .80 4.49 49,600 .82 4.69 45,700 .84 4.77 43,600 .86 5.02

Cooling Performance with Extended Ratings

** = B, L, BC, LC
* = B, L

D&S

Advertising
This manual is related to the following products:

B, LC, L, 2AC14