ABUS Technologies Field Logger Data Acquisition/Recorder User Manual

Page 14

Advertising
background image

ABUS TECHNOLOGIES INC.

14

Field

Logger

Registers 01 to 08:

It holds the most recent measurements on the channels. The channel update rate depends on

the number of active channels and on the input types configured in the channels. The Field Logger

updates the readings at the maximum possible rate (limited to the A/D conversion time).

The channels configured for Pt100 take twice the time to deliver a new conversion, since it

performs two conversions in sequence (cable length compensation).

When only one channel is active, the time needed for updating the channel is 0.2 seconds (best

case). When 8 channels are configured as Pt100, the update of the 8 channels takes 0.95s (worst

case). The returned value is in 2’s complement.

For Pt100 readings, where the resolution is 1/10

th

of a degree, the decimal point is not

transmitted, due to protocol limitations. Likewise, the decimal point is disregarded for the linear inputs

(4-20mA and 0-50mV).

Register 09:


Reports the alarm status, as drawn below:

Byte high:

Byte High

Byte low:

Byte Low