Example: AC cable

If overlength AC or DC cables are to be laid
in loops in the connection area, attach the
cables with cable ties to the eyelets provi-
ded on the top and bottom of the connec-
tion block.

Maximum fuse
rating on alternat-
ing current side

Inverter

Phases

AC power

Maximum

fuse rating

Recommended

fuse rating

Fronius Symo 10.0-3-M

3

10000 W

1 x C 63 A

1 x C 25 A

Fronius Symo 12.5-3-M

3

12500 W

1 x C 63 A

1 x C 32 A

Fronius Symo 15.0-3-M

3

15000 W

1 x C 63 A

1 x C 32 A

Fronius Symo 17.5-3-M

3

17500 W

1 x C 63 A

1 x C 40 A

Fronius Symo 20.0-3-M

3

20000 W

1 x C 63 A

1 x C 50 A

NOTE! Local regulations, the energy supply company or other factors may re-
quire an earth-leakage circuit breaker in the grid line. For this situation, a type A
earth-leakage circuit breaker with a tripping current of at least 100 mA is generally
adequate. In particular cases, and depending on local factors, however, the type
A earth-leakage circuit breaker may trip at the wrong time. For this reason, Fron-
ius recommends that an earth-leakage circuit breaker that is suitable for frequen-
cy converters should be used.

max. C 63 A

AC ~

RCD

National Standards

?

Type A

YES

I

ΔN

≥ 100 mA

§