Charging errors

Ready indicator lit, error indicator flashing, SOC indicator 1/2/3/4 flashing:

Cause:

Timeout in the corresponding charging phase or battery capacity too high

Remedy:

Select correct characteristic type according to the enclosed characteris-
tic data sheet and charge again

Cause:

Battery faulty (cell short circuit, heavy sulphation)

Remedy:

Check battery and replace if necessary

Cause:

Optional external temperature sensor has tripped due to over- or under-
temperature

Remedy:

Allow battery to cool, or charge battery in a more suitable area