ifm electronic RM9000 User Manual

Page 23

Advertising
background image

UK

CANopen encoder

23

7.5 Device-profile-specific objects from 6000h to 9FFFF

Index S-Idx Name

Type,

access

default value

Description

6000

Operating

parameters

u16, rw

1h

The object sets the counting direction,

the diagnostic function and the scaling

function�
Note: The counting direction is always

seen looking at the shaft� With clockwise

direction of the shaft (CW) the counting

direction is increasing�

Scaling function:
Using the scaling function the position value provided can be adapted to the requirements of

the application via the software� The objects 6001 and 6002 of the device profile are scaling

parameters� When the scaling bit has been set to zero, scaling is switched off�
Bit structure

Bit

15

14

13

12

11���4 3

2

1

0

Description

MS

MS

MS

MS

R

MD

SFC CD

CS

Abbreviations:
MS = manufacturer-specific function (not available)
R = reserved
MD = measurement direction (not available)
SFC = scaling function (0 = off, 1 = on)
CD = commissioning diagnostic control (not available)
CS = counting direction 0 = CW (clockwise); 1 = CCW (counter-clockwise)

6001

0

Measuring

units per

revolution

u32, rw

see

type label

Setting steps per revolution

6002

0

Total

measuring

range in

measuring

units

u32, rw

see

type label

Setting the total resolution of the

measuring range

6003

0

Preset value

u32, rw

0

Setting the preset value for the encoder

6004

0

Position value

u32,

romap

-

The object gets the position value

6030

Speed value

If the max� possible value is exceeded,

the value stops there� The user can use

the object 3010 (32 bits)�

0h

Number of sub

indices

u8, ro

1h

1h

Speed value

channel 1

integer

16, romap

-