Legrand AL3356-ACTLPB Small Aluminum Surface Raceway User Manual

Al3300 aluminum surface raceway, Installation instructions

Advertising
background image

AL3300 RACEWAY CABLE FILL CAPACITIES FOR DATA/COMMUNICATION

OD

W/O Divider

W/Offset Divider

W/Half Divider

CABLE/WIRE SIZE

[In.]

[mm]

(4.75 sq. in.)

(.95 sq. in.)

(2.08 sq. in.)

20%*

40%**

20%*

40%**

20%*

40%**

UNSHIELDED

4-pair,

24 AWG, Cat.5

0.220

[5.6]

24

49

4

9

10

21

TWISTED PAIR

4-pair,

24 AWG, Cat.3

0.190

[4.8]

33

67

6

13

14

29

4-pair,

24 AWG, Cat.6

0.250

[6.3]

19

38

3

7

8

16

TELEPHONE

2-pair,

24 AWG

0.140

[3.6]

61

123

12

24

27

54

3-pair,

24 AWG

0.150

[3.8]

53

107

10

21

23

47

4-pair,

24 AWG

0.190

[4.8]

33

67

6

13

14

29

25-pair,

24 AWG

0.410

[10.4]

7

14

1

2

3

6

COAXIAL

RG58/U

0.195

[5.0]

31

63

6

12

13

27

RG59/U

0.242

[6.1]

20

41

4

8

9

18

RG62/U

0.242

[6.1]

20

41

4

8

9

18

RG6/U

0.270

[6.9]

16

33

3

6

14

TWINAXIAL

100 Ohm

0.330

[8.4]

11

22

2

4

4

9

SHIELDED Type

1

0.390

[9.9]

7

15

1

3

3

6

TWISTED PAIR

Type 2

0.465

[11.8]

5

11

1

2

2

4

Type 3

0.245

[6.2]

20

40

4

8

8

17

FIBER OPTIC

Two Standard (Duplex)

0.190

[4.8]

33

67

6

13

14

29

Multimedia, 62.5/125 um

AL3300 Aluminum
Surface Raceway

INSTALLATION INSTRUCTIONS

Installation Instruction No.: INST014 R2 – Updated April 2005

NOTE: * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict

cross sectional area.

** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.

Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.

All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.

Note: Raceway may be configured in single or multiple channels

to accommodate power or communications wiring.

MAXIMUM CROSS SECTION

2 7/8"

[70mm]

1 7/8"

[48mm]

AL3300 RACEWAY WIRE FILL CAPACITIES FOR POWER

CAPACITY OF CROSS SECTIONAL AREA

WITH OFFSET

WITHOUT

WITH HALF

WITHOUT

DIVIDER

OFFSET DIVIDER

DIVIDER

HALF DIVIDER

WIRE TYPE

6 AWG

10

24

17

33

THWN/THHN

8 AWG

14

33

23

47

10 AWG

28

66

47

95

12 AWG

44

104

74

150

14 AWG

60

140

99

202