Legrand AL5200 Series Large Multi-Channel Aluminum Surface Raceway User Manual

Al5200 aluminum surface raceway, Installation instructions

Advertising
background image

AL5200 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATION

CAPACITY CROSS SECTIONAL AREA

CABLE/WIRE SIZE

OD

8.5" [216mm]

4.85" [122mm]

3.78" [89mm]

3.86" [99mm]

4.36" [114mm]

Inches

[mm]

20%*

40%**

20%*

40%**

20%*

40%**

20%*

40%**

20%*

40%**

UNSHIELDED

4-pair, 24 AWG,cat.3

0.190

[4.8]

60

20

34

68

26

53

27

54

30

61

TWISTED PAIR

4-pair, 24 AWG,cat.4

0.220

[5.6]

44

89

25

51

19

39

20

40

22

45

4-pair, 24 AWG,cat.5

0.250

[6.3]

34

69

19

39

15

30

17

31

17

35

TELEPHONE

2-pair, 24 AWG

0.140

[3.6]

10

221

63

126

49

98

50

100

56

113

3-pair, 24 AWG

0.150

[3.8]

96

193

54

109

42

85

43

87

49

98

4-pair, 24 AWG

0.190

[4.8]

60

120

34

68

26

53

27

54

30

61

25-pair, 24 AWG

0.410

[10.4]

12

125

7

14

5

11

5

11

6

13

COAXIAL

RG58/U

0.195

[5.0]

57

114

32

64

25

50

25

51

29

58

RG59/U

0.242

[6.1]

37

74

21

42

16

32

16

33

18

37

RG62/U

0.242

[6.1]

37

74

21

42

16

32

16

33

18

37

RG6/U

0.270

[6.9]

29

59

16

33

13

26

13

26

15

30

TWINAXIAL

100 Ohm

0.330

[8.4]

19

39

11

22

8

17

9

18

10

20

SHIELDED

TYPE 1

0.390

[9.9]

14

28

8

16

6

12

6

12

7

14

TWISTED PAIR

TYPE 2

0.465

[11.8]

10

20

5

11

4

8

4

9

5

10

TYPE3

0.245

[6.2]

36

72

20

41

20

32

16

32

18

36

FIBER OPTIC

Two Standard(Duplex)
Multimode, 62.5/125um

0.190

[4.8]

60

120

34

68

26

53

27

54

30

61

AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER

CAPACITY OF CROSS SECTIONAL AREA

WITH OUT DEVICE

WIRE TYPE

2.4" [61mm]

2.85" [72mm]

3.5" [85mm]

3.9" [99mm]

4.5" [114mm]

4.8" [122mm]

8.5" [216mm]

THWN/THHN

#6

18

22

27

30

34

37

65

#8

25

30

37

42

48

51

91

#10

52

62

76

84

98

104

184

#12

82

97

119

113

154

164

290

#14

110

131

161

179

207

220

391

AL5200 Aluminum
Surface Raceway

INSTALLATION INSTRUCTIONS

AL5200 RACEWAY WIRE FILL CAPACITIES FOR POWER

CAPACITY OF CROSS SECTIONAL AREA

WITH DUPLEX DEVICE (1.34 Sq.in.)

WIRE TYPE

3.78" [89mm]

3.86" [99mm]

4.36" [114mm]

4.85" [122mm]

8.5" [216mm]

THWN/THHN

#6

16

19

24

26

55

#8

23 27

34

37

76

#10

47

55

68

75

155

#12

74

87

108

118

244

#14

99

117

145

159

329

NOTE: * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict

cross sectional area.

** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.

Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.

All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.

Note: Raceway may be configured in single or multiple channels
to accommodate power or communications wiring.

MAXIMUM CROSS SECTION

8.5 sq. in.

[215.90mm]

5"

[127mm]

2 3/4"

[70mm]

2 3/16"

[56mm]

2"

[51mm]

4.86 sq. in.

[123.19mm]

3.78 sq. in.

[96.01mm]

3.90 sq. in.

[99.06mm]

4.50 sq. in.

[114.30mm]