TROUBLESHOOTING

Load will not turn on:

• LED does not flash:
‑ Check the sensitivity for proper configuration.

‑ Check all wire connections. Verify the ground wire is tightly secured.

• LED does flash:
‑ Press the ON/OFF button. If load does not turn on, check all wire

connections and verify the load wire is tightly secured.

‑ Check the light level trimpot. Turn it fully clockwise
• If load still does not turn on, call 800.223.4185 for technical support.

Load will not turn off:

• The time delay can be set for 30 seconds

(Walk Test), 5, 10, 15, 20, 25, or 30 minutes.

Ensure that the time delay is set to the

desired delay and that there is no movement

within the sensor’s view for that time period.

• To quickly test the unit for proper operation,

turn the time delay to minimum (fully

counterclockwise) and move out of the

sensor’s view. Load should turn off after

30 seconds.

• If load still does not turn off, call

800.223.4185 for technical support.

Sensing motion outside desired area:

• Opaque adhesive tape is included with the

sensor and can be used to limit the detection areas. See Masking the Lens.

• Adjust sensitivity counterclockwise to reduce excessive sensitivity.

WSP‑250

Passive Infrared Wall Switch

Occupancy Sensor

SPEcIfIcaTIONS

WSP-250 Voltages .................................................120 or 277VAC, 60Hz

Load Requirements

@ 120VAC, 60Hz ............. 0‑800W ballast & tungsten, 1/6 hp

@ 277VAC, 60Hz ........................................... 0‑1200W ballast

Time Delay Adjustment ...................................30 seconds ‑ 30 minutes

Sensitivity Adjustment ...........................................Minimum‑Maximum
Light Level Adjustment ..................................................... 10 ‑ 200 + FC

SENSOR adjUSTmENT

dO NOT OVERTURN TRImPOTS WHEN adjUSTING THE SENSOR!

1. To test unit operation, press the ON/OFF button to turn the load on.
2. Remove the button cover to access the adjustment controls. Use a small,

flat blade screwdriver to press down the locking tab at the top of the button,
then gently pry it off.
a) Set the time delay to the “walk test” position (fully counterclockwise).
b) Leave the room. The load should go off after 30 seconds.

3. To test sensitivity:

a) Make no motion for 3 seconds.
b) Wave your hand sideways in front of the sensor at a distance of

approximately 12". The LED blinks when movement is detected.
Typically, the sensitivity should be at maximum (fully clockwise).

4. Set the light level when the controlled light would normally be turned off

due to the presence of sufficient daylight or other electric light. [If this
feature is not needed, leave the light level at maximum (fully clockwise)].
a) Set the Time Delay to at least 5 minutes. This takes the sensor out of

Walk‑test mode, and enables the light level feature.

b) Set the Light level to 50% (12 o’clock position) which is approximately

100fc. Let the sensor time out so lights are off. Enter the space and
lights should remain off.

c) Make sure your body does not cast a shadow on the sensor, and adjust

the light level trimpot clockwise in small increments.

d) After each adjustment, wait 5‑10 seconds to see if the lights turn on.

Repeat until the lights turn on. At this setting the load connected to the
sensor will not turn on if light levels are above the current illumination.

Note: Users can override this function by placing their hand in front of the

sensor to block incoming light. The load will then remain on until the
space is unoccupied or the light level rises above the setpoint and the
time delay expires.

5. Reset the time delay to the

desired setting. The time delay
can be set from 30 seconds
(see Walk‑test feature, light
level feature is disabled)
to 30 minutes in 5‑minute
increments.

call 800.223.4185 for Technical Support

WaRRaNTy INfORmaTION

Pass & Seymour/Legrand warranties its products to be free of defects
in materials and workmanship for a period of five (5) years. There are
no obligations or liabilities on the part of Pass & Seymour/Legrand for
consequential damages arising out of, or in connection with, the use or
performance of this product or other indirect damages with respect to loss of
property, revenue or profit, or cost of removal, installation or reinstallation.

In

sta

lla

tio

n I

ns

tr

uc

tio

ns

P.O. Box 4822, Syracuse, NY 13221‑4822

Technical Support: 800.223.4185

www.passandseymour.com

340886 11343

Please

Recycle

Visit our website: www.passandseymour.com

Sensitivity (S)
shown as set
for Maximum

Light Level (L)
shown as set
for Maximum (+)
to disable

Time Delay (T)
Shown as set for
15 minutes

Time Delay (T)

Shown as set for

15 minutes

30 seconds
(Walk-test)

5 minutes

10 minutes

20 minutes

25 minutes

30 minutes

L

T

S

WSP250 IS_340886 11343.indd 1-4

3/30/09 9:19:49 AM

Advertising