Jordan Valve Mark 4150 Series Pressure Controllers User Manual

Page 2

Advertising
background image

M

ark

4150

and

4160 S

erieS

P

reSSure

C

ontrollerS

-2-

Operation

Although the output for these controllers are set prior

to shipping, upon arrival the following items should be

checked.

Bellofram Mark 50 Filter Regulator

Bellofram Mark 50 Filter Regulator is a self-contained

filter regulator designed to deliver air or gas to the

pilot at a constant pressure. The Bellofram Mark 50 is

designed to handle inlet pressures up to 250 psi. The

Series 4150/4160 delivers an outlet pressure of 3 - 15

psi when the regulator is set to 20 and it will deliver 6-30

psi output when the regulator is set to 35 psi.

The filter component ensures that operation is clean and

dry.

The relief valve is geared to open when the pressure is

reduced to 1 psi above the regulator set point.

Releasing the lock nut and adjusting the adjusting screw

located on the top of the regulator can reduce pressure

setting for the regulator.

Proportional Controllers

Most of the proportional controls will be used in applica-

tions that require a band set to approximately 15%. The

following steps are used to test this setting.

1.

The air supply should be connected to Bello-

fram Mark 50 filter regulator.

2.

Zero the pressure setting dial.

3.

Set the proportional band adjustment to 15%

4.

There should be no pressure sent to the mea

suring element.

5.

For direct or reverse acting controllers the

range and output should be set as follows.

Proportional-Reset Controllers

1.

The reset dial should be set to maximum.

2.

The air supply should be connected to Bello-

fram Mark 50 filter regulator.

3.

Zero the pressure setting dial and proportioned

setting dial.

4.

There should be no pressure sent to the mea-

suring element.

5.

For direct or reverse acting controllers the

range and output should be as follows.

Range

Output

3-15 psi

8-10 psi

6-30 psi

16-20 psi

Range

Output

3-15 psi

8-10 psi

6-30 psi

16-20 psi

Start Up

Proportional Controllers

1.

The air supply should be connected to Bellofram

Mark 50 filter regulator.

2.

Connect the control pressure line and open the

lock shield needle valve.

3.

Ensure all piping and connections are free from

leaks.

4.

Set the pressure to the desired control point.

5.

Proportional band should be set at 15% of the

bandwidth.

6.

Open the manual control valves that are up

stream and downstream, at the same time close

the by-pass valves.

7.

Set the controller near the desired control point.

When it reaches that point, begin to broaden the

proportional band. Broaden the band as little

as possible. The narrowest band that

will not result in cycling provides

the best control. This band adjustment

will affect the zero. Re-zero the unit.

8.

Test the bandwidth by changing the pressure

setting adjustment for a moment. If this

causes cycling, then broaden the proportional

band and test again. This procedure is

to be repeated until stability is reached.

Advertising