Response by Control Type—Advanced Microprocessor Controls

40

5.4

Analog Sensors

5.4.1 Connecting the Analog Sensors

The sensor inputs are factory-set to accept a 4 - 20 mA signal. The inputs can be changed by removing

the appropriate jumpers on the control circuit board. See Table 13, Figure 5 and Figure 6.
The user supplied analog sensors MUST have their own power supply. To reduce the effects of inter-

ference from any noise source, the sensor input wiring should be shielded twisted pair and the shield

tied to earth ground at one end.
Analog input terminals for field connections are factory wired to the microprocessor board if specified

when ordered. Eight terminals are located in the field wiring compartment of the unit. Wire sensors

to the terminals as follows:

Consult your Liebert supplier for a field installation kit to add these connections after, if required.

Figure 5

Analog input jumpers

Table 13

Changing factory-set sensor inputs

Terminal

Signal

41

Input #1 (+)

42

Input #1 (-)

43

Input #2 (+)

44

Input #2 (-)

45

Input #3 (+)

46

Input #3 (-)

47

Input #4 (+)

48

Input #4 (-)

Table 14

Additional connections available after unit delivery

Input #1

Input #2

Input #3

Input #4

4–20 mA

Jumper P50.1&2 and

P50.3&4

Jumper P50.5&6 and

P50.7&8

Jumper P50.9&10 and

P50.11&12

Jumper P50.11&14 and

P50.15&16

0–5 VDC

Jumper P50.1&2

Jumper P50.5&6

Jumper P50.9&10

Jumper P50.13&14

0–10 VDC

No jumper on

P50.1&2 and P50.3&4

No jumper on

P50.5&6 and P50.7&8

No jumper on

P50.9&10 and P50.11&12

No jumper on

P50.11&12 and P50.15&16

Analog input jumper location

ENLARGED AREA