3 function 2 group [fu2 – HP 30 HP30 User Manual

Page 66

Advertising
background image

Chapter 5 - Parameter List

5-6

5.3 Function 2 Group [FU2]

Keypad Display

Setting Range

Code

Description

LCD

7-Segment

LCD

7-Segment

Units

Factory

Default

Adj.

During

Run

Page

FU2-00 Jump to desired code #

Jump code

Not displayed

1 to 94

Not available

1

1

Yes

6-2

FU2-01 Previous Fault History 1

Last trip-1

01

FU2-02 Previous Fault History 2

Last trip-2

02

FU2-03 Previous Fault History 3

Last trip-3

03

FU2-04 Previous Fault History 4

Last trip-4

04

FU2-05 Previous Fault History 5

Last trip-5

05

By pressing [PROG] and [▲] key,

the frequency, current, and

operational status at the time of fault

can be seen.

- None -

No 0

FU2-06 Erase Fault History

Erase trips

06

Yes 1

- No Yes

6-2

FU2-07 Dwell Frequency

Dwell freq

07

FU1-22 to FU1-20

0.01

5.00 [Hz]

No

FU2-08 Dwell Time

Dwell time

08

0 to 10 [sec]

0.1

0.0 [sec]

No

6-2

No 0

FU2-10

Frequency Jump
Selection

Jump freq

10

Yes 1

- No No

FU2-11

17

Jump Frequency 1 Low

Jump lo 1

11

FU1-22 to FU2-12

0.01 10.00 [Hz]

No

FU2-12 Jump Frequency 1 High

Jump Hi 1

12

FU2-11 to FU1-20

0.01 15.00 [Hz]

No

FU2-13 Jump Frequency 2 Low

Jump lo 2

13

FU1-22 to FU2-14

0.01 20.00 [Hz]

No

FU2-14 Jump Frequency 2 High

Jump Hi 2

14

FU2-13 to FU1-20

0.01 25.00 [Hz]

No

FU2-15 Jump Frequency 3 Low

Jump lo 3

15

FU1-22 to FU2-16

0.01 30.00 [Hz]

No

FU2-16 Jump Frequency 3 High

Jump Hi 3

16

FU2-15 to FU1-20

0.01 35.00 [Hz]

No

6-2

FU2-17

Start Curve for S-Curve
Accel/Dedel Pattern

Start Curve

17

1 to 100 [%]

1

40%

No

FU2-18

End Curve for S-Curve
Accel/Dedel Pattern

End Curve

18

1 to 100 [%]

1

40%

No

6-2

FU2-19

Input/Output Phase Loss
Protection

Trip select

19

00 to 11
(Bit Set)

- 00 Yes

6-2

No 0

FU2-20 Power ON Start Selection Power-on run

20

Yes 1

- No Yes

6-2

No 0

FU2-21 Restart after Fault Reset

RST restart

21

Yes 1

- No Yes

6-2

FU2-22 Speed Search Selection Speed Search

22

0000 to 1111

(Bit Set)

- 0000 No

FU2-23

Current Limit Level
During Speed Search

SS Sup-Curr

23

80 to 200 [%]

1

100 [%]

Yes

FU2-24

P Gain
During Speed Search

SS P-gain

24

0 to 30000

1

100

Yes

FU2-25

I Gain
During speed search

SS I-gain

25

0 to 30000

1

1000

Yes

6-2

FU2-26

Number of Auto Restart
Attempt

Retry number

26

0 to 10

1

0

Yes

6-2

17

Code FU2-11 through FU2-16 appears only when FU2-10 is set to ‘Yes’.

Advertising