hubbell industrial controls, inc.
LX301 Solid State Control Module
Control Module Features
¾
2PDT contacts for engine start signals
¾
Module is adjustable from 120-600V, 50-60Hz
¾
Quick disconnect plugs for easy removal
Voltage & Frequency Sensing
¾
Adjustable close differential voltage sensing of all phases of normal source
¾
Pick-up voltage adjustment from 85% to 100%
¾
Drop out voltage adjustment from 75% to 98% of pick-up
¾
Voltage and frequency sensing on all phases of emergency
¾
Voltage adjustable from 85% to 100% of nominal
¾
Frequency adjustable from 90% to 100% of nominal
¾
Voltage and Frequency sensing available for single or three phase operation
Status LED’s:
¾
Normal source voltage available
¾
Emergency source voltage available
¾
Emergency source frequency okay
¾
Transfer to emergency timing
¾
Retransfer to normal timing
¾
Engine cool-down timing
Field adjustable
¾
Time delay to override momentary normal source outages to delay all transfer switch and engine-starting signals—
adjustable zero to six seconds
¾
Transfer to emergency time delay—adjustable from zero to five minutes for controlled timing of load transfer to
emergency
¾
Retransfer to normal time delay—adjustable two to 30 minutes with automatic bypass if emergency source fails
¾
Time delay for running engine unloaded (cool-down)—adjustable from two to thirty minutes