4. TECHNICAL CHARACTERISTICS

GEK-106168E

DBF Breaker Failure Protection

21

4.

4.

4.

4.

TECHNICAL CHARACTERISTICS

TECHNICAL CHARACTERISTICS

TECHNICAL CHARACTERISTICS

TECHNICAL CHARACTERISTICS

4.1. MODEL LIST

Position

DBF

1

-

-

-

-

1

1

-

-

0

0

A

Description

Comm. Interface

0

P2: RS232 + P3: RS232

5

1

P2: RS232 + P3: Plastic F.O.

2

P2: RS232 + P3: Glass F.O.

3

P2: RS232 + P3: RS485

6

Ranges

[[[[

1

]]]]

See Table

[

1R

]

Comm. Protocols

7

1

P1, P2, P3: Mlink

2

P1, P2: Mlink; P3: ModBus
Language

8

M

Spanish

D

English
Model

11

0

Basic Model

1

Enhanced Model (Expansion
board)
Power Supply

12

G

48-125 VDC

H

110-250 VDC

13,14

0

0

Special Models

15

A

Revision

TABLE

[[[[

1R

]]]]

- RANGES

MODELS

A

B

C

D

E

F

G

DBF

PHASE

1-12 A

0.2-2.4 A

1-12A

1-12 A

1-12 A

0.5-6 A

0.5-6 A

GROUND

1-12 A

0.2-2.4 A

0.2-2.4 A

0.5-6 A

0.1-1.2 A

0.2-2.4 A

0.1-1.2 A

4.1.1. SPECIAL MODELS

The input voltage of the standard model corresponds to the Power Supply voltage. The following models have
been developed to allow the selection of an input voltage independently of the Power Supply.

The following codes should be placed as two last digits before A in the ordering code for selecting the desired
characteristics:

MOD 04:

V inputs: 48 Vdc

±

20%

MOD 05:

V inputs: 110 Vdc

±

20%

MOD 06:

V inputs: 125 Vdc

±

20%

MOD 07:

V inputs: 250 Vdc

±

20%

Example: If we want to order a relay model with a digital input voltage of 48 Vdc, the model should be:
DBF1*****11**04A.