1.2 SPECIFICATIONS

• NOTE: Specifications are subject to minor change without notice for further improvement.

—3—

MODELS

ITEMS

COOLING CAPACITY (BTU/h)

5,300

5,200

5,200

6,000

6,000

POWER SUPPLY (Phase, V, Hz)

1ø, 115V, 60HZ

INPUT (W)

530

470

610

620

OPERATING CURRENT (AMP.)

4.8

4.3

5.6

5.8

REFRIGERANT CONTROL

CAPILLARY TUBE

REFRIGERANT CHARGE (R-22)

230g (8.1 Oz )

330g(11.6 Oz) 335g (11.8 Oz) 235g (8.3 Oz)

INSIDE FAN

TURBO

OUTSIDE FAN

PROPELLER FAN WITH SLINGER RING

AIR DISCHARGE

2-WAY (RIGHT AND LEFT)

CHASSIS

TOP-DOWN

PROTECTOR

TEMPERATURE CONTROL

THERMISTOR

ROTARY SWITCH

5 POSITIONS (LOW FAN, HIGH FAN, OFF, HIGH COOL, LOW COOL)

FAN MOTOR

6 POLES, 16W

6 POLES, 21.3W

6 POLES, 24W

6 POLES, 21.4W

• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR

M5403R

M5203R

M5203L

M6003R

WM-6011

LWJ0611PCG

LWC061JGMK1

1.3 SAFETY PRECAUTIONS

1. When servicing, set the POWER of CONTROL

BOARD to Off and unplug the power cord.

2. Observe the original lead dress.

If a short circuit is found, replace all parts which
have been overheated or damaged by the short cir-
cuit.

3. After servicing, make an insulation resistance test

to prevent the customer's exposure to shock
hazards.

1.4 INSULATION RESISTANCE TEST

1. Unplug the power cord and connect a jumper

between 2 pins (black and white).

2. The grounding conductor (green or green and yel-

low) is to be open.

3. Measure the resistance value with an ohm meter

between the jumpered lead and each exposed
metallic part on the equipment at all Mode [except
POWER OFF].

4. The value should be over 1 M

.