Installation Instructions

DIRECT CONNECT APPLICATIONS

MAKE WIRE LEAD CONNECTIONS INSIDE THE JUNCTION BOX

1.

Make all wire connections by using appropriate UL-listed electrical connectors and techniques.

2.

Select the applicable wiring situation and follow the instructions accordingly:

3.

Be sure that all wire leads are inside the junction box and not

pinched between the box and the unit. The green insulated

ground wire from the Zoneline MUST be connected to the branch

circuit ground wire.

4.

Plug the 9-pin connector into the 9-pin receptacle in the junction box.

5.

Replace the junction box cover by replacing the two screws

removed earlier.

3

230/208 Volt

Wall Plug

Heater Wattage

Power Supply Kits

Configuration

Circuit Protective Device

@ 230/208 Volts

RAK3152

Tandem

15-Amp Time-Delay Fuse or Breaker

2.55/2.09 KW

RAK3202

Perpendicular

20-Amp Time-Delay Fuse or Breaker

3.45/2.82 KW

RAK3302

Large Tandem

30-Amp Time-Delay Fuse or Breaker

5.00/4.10 KW

230/208 Volt

Heater Wattage

Power Supply Kits

@ 230/208 Volts

Circuit Protective Device

RAK4157

2.55 KW/2.09 KW

15-Amp Time-Delay Fuse or Breaker

RAK4207

3.45 KW/2.82 KW

20-Amp Time-Delay Fuse or Breaker

RAK4307

5.00 KW/4.10 KW

30-Amp Time-Delay Fuse or Breaker

265 Volt

Heater Wattage

Power Supply Kits

@ 265 Volts

Circuit Protective Device

RAK5157

2.55 KW

15-Amp Time-Delay Fuse or Breaker

RAK5207

3.45 KW

20-Amp Time-Delay Fuse or Breaker

RAK5307

5.00 KW

30-Amp Time-Delay Fuse or Breaker

Conduit

Make wire lead

connections

1-Phase 220-240 VAC

When connecting the Zoneline to a single-phase circuit

for 230V applications:

Connect the white and black leads of the Zoneline

power supply kit to the branch circuit L1 and L2 leads.

(The white lead of the power supply kit should be

identified by the installer using electrical tape with some

color other than green or white.) Connect the green lead

of the power supply kit to the power supply and branch

circuit ground.

3-Phase 208 VAC

When connecting the Zoneline to a three-phase circuit

for 208V applications:

Connect the white and black leads of the Zoneline

power supply kit to the branch circuit L1 and L2 leads.

(The white lead of the power supply kit should be

identified by the installer using electrical tape with some

color other than green or white.) Connect the green lead

of the power supply kit to the power supply and branch

circuit ground.

3-Phase 208 VAC with “Crazy Leg”

When connecting the Zoneline to a three-phase circuit

with “Crazy Leg” for 208V applications:

Connect the white and black leads of the Zoneline

power supply kit to the branch circuit Neutral and L1

leads. (The white lead of the power supply kit should

be connected to neutral.) Connect the green lead of

the power supply kit to the power supply and branch

circuit ground.

3-Phase 253-277 VAC

When connecting the Zoneline to a three-phase circuit

for 265V applications:

Connect the white and black leads of the Zoneline

power supply kit to the branch circuit Neutral and L1

leads. (The white lead of the power supply kit should

be connected to neutral.) Connect the green lead of

the power supply kit to the power supply and branch

circuit ground.

Power Cord Connections

POWER CONNECTION CHART

Direct Connections