APPENDIX B ELECTRICAL DATA

ATTENTION INSTALLING PERSONNEL

Use only the heater kit specified for each model as dictated by the table above.

MIN

MAX

Qty

RLA

LRA

Qty

HP

RLA

HP

FLA

208/230-60-3

187

253

2

33.3

239.0

3

1/3

2.40

BD STD STATIC

5.0

12.7

460-60-3

414

506

2

17.9

125.0

3

1/3

1.20

BD STD STATIC

5.0

6.4

575-60-3

518

633

2

12.8

80.0

3

1/3

0.90

BD STD STATIC

5.0

5.1

20 TON

ELECTRICAL DATA

ID MOTOR APPL

COMPRESSOR

(ea)

OD FAN MOTORS

(ea)

ID FAN

MOTOR

VOLTAGE

LIMITATIONS

VOLTAGE

(NAMEPLATE)

MODELS

NOTE: See unit nameplate for proper overcurrent protection.

When using electric heat kit, use of the single point kit installed in the unit is required to meet UL requirements

MIN

MAX

Qty

RLA

LRA

Qty

RLA

LRA

Qty

HP

RLA

HP

FLA

208/230-60-3

187

253

1

29.5 195.0

1

25.0

164.0

3

1/3

2.40

BD STD STATIC

3.0

9.2

460-60-3

414

506

1

14.7

95.0

1

12.2

100.0

3

1/3

1.20

BD STD STATIC

3.0

4.6

575-60-3

518

633

1

12.2

80.0

1

9.0

78.0

3

1/3

0.90

BD STD STATIC

3.0

4.2

MODELS

15 TON

SMALLER

COMPRESSOR

ELECTRICAL DATA

ID MOTOR

APPL

LARGER

COMPRESSOR

OD FAN MOTORS

(ea)

ID FAN MOTOR

VOLTAGE

LIMITATIONS

VOLTAGE

(NAMEPLATE)

UNIT

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

HEATER KIT

MODEL NUMBER

MINIMUM CFM

Downshot

EHK3-31

5250

EHK4-31

5250

EHK7-31

5250

15 TON

EHK3-46

5250

EHK4-46

5250

EHK7-46

5250

EHK3-60

5250

EHK4-60

5250

EHK7-60

5250

EHK3-31

7000

EHK4-31

7000

EHK7-31

7000

20 TON

EHK3-46

7000

EHK4-46

7000

EHK7-46

7000

EHK3-60

7000

EHK4-60

7000

EHK7-60

7000

EHK3-75

7000

EHK4-75

7000

EHK7-75

7000