4 example configuration, 4 example configuration -9 – MITSUBISHI ELECTRIC FX2N User Manual

Page 19

Advertising
background image

FX2N-32DP-IF Profibus-DP Interface Unit

Introduction 1

1-9

1.3.4

Example Configuration

Figure 1.5: Example Configuration

For configuration rules, refer to section 1.3.3.

1) Check special function blocks.

a) Count special function blocks.

This 32DP-IF has 3 special function blocks connected (FX

2N

-4AD

×

1, FX

2N

-4DA

×

2).

This configuration is OK as the total number of blocks is less than 8.

b) Check the loading on the 5 V DC bus supply. Consumption values for special function

blocks can be found in Table 1.7. For maximum available current see the Table 1.6.

This configuration is OK as the 5 V DC bus supply consumption value is less than 220 mA
(5 V DC bus supply capacity).

However, this system needs a supply of 455 mA from an external 24 V DC power supply, for
the special function blocks. In this case, the 32DP-IF can supply 250 mA for external 24 V
DC. See next page (check the loading on the 24 V DC service supply)

Table 1.8: Check 5 V DC Bus Supply

Items

Internal 5 V DC

External 24 V DC

FX

2N

-4AD

30 mA

55 mA

FX

2N

-4DA

30 mA

200 mA

FX

2N

-4DA

30 mA

200 mA

Total Consumption Values

90 mA <220 mA

455 mA

Profibus-DP
network

FX

2N

-

32DP-IF

FX

2N

-

4AD

FX

2N

-16EX

-ES/UL

FX

2N

-

4DA

FX

2N

-16EYT

-ESS/UL

FX

2N

-

4DA

A Series

PLC

A1SJ71PB92 (software version E)

Advertising