Users manual – MGE UPS Systems EPS 7000 User Manual
Page 25
Introduction
page 1 — 15
Users Manual
C: Rectifier/charger fault
This red LED indicates an alarm condition within the rectifier/battery charger. It indicates the presence of one of the
following fault conditions:
◗
Input circuit breaker Q1 open
◗
Input power protection fuse blown
◗
Rectifier/battery charger over-temperature
◗
Battery charge overcurrent
◗
Battery overvoltage
◗
Rectifier/battery charger control board fault
◗
Power supply board fault
D: Main AC input (mains 1) outside tolerance
This orange LED indicates that the main AC input (mains 1) source is outside tolerance (voltage and/or frequency
too high or too low).
E: Reserved for future use.
F: Battery temperature outside tolerance
This orange LED indicates that the ambient temperature of the battery is too high or too low.
G: Battery charging
This orange LED indicates that the battery is being recharged. This LED functions only when the connected battery
is of the vented lead-acid type (sealed lead-acid batteries will not activate this signal).
H: Inverter fault
This red LED indicates an alarm condition in the inverter, which may be one or more of the following conditions:
◗
Inverter shutdown due to output voltage out of tolerance
◗
Inverter output protection fuse blown
◗
Inverter leg fault
◗
Inverter output transformer over-temperature
◗
Inverter leg over-temperature
◗
Internal clock fault
◗
Inverter control board fault
◗
Power supply board fault
I:
Battery discharged
This orange LED indicates that the battery has reached the end of its autonomy, shutting down the inverter.
J:
Inverter desynchronized
This orange LED indicates that the inverter is not synchronized with the bypass AC input (mains 2).