SIGnature coMManD - cHecK GaS preSSure and eLectrIcaL InStaLLatIon

1. Check gas type. The gas supply must be the same as

stated on the appliance’s rating decal. If the gas supply
is different from the fireplace, Stop! Do not install the
appliance. Contact your dealer immediately.

2. To ease installation, a 24" (610 mm) flex line with manual

shut-off valve has been provided with on this appliance.
Install and attach 1/2" gas line onto shut-off valve.

3. After completing gas line connection, purge air from

gas line and test all gas joints from the gas meter to the
fireplace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.

4. To check gas pressures at valve, turn captured screw

counter clockwise 2 or 3 turns and then place tubing
to pressure gauge over test point. Turn unit to high.
Figure 44. After taking pressure reading, be sure and
turn captured screw clockwise firmly to reseal. Do not
over torque. Check test points for gas leaks.

FP1909a
signature command valve
alternate view
8/08

Pressure Inlet

Pressure Outlet

Pilot Adjust-
ment Screw

FP1909a

Figure 44 -
Signature Command Valve

eLectrIcaL wIrInG

General

1. This fireplace is equipped with the Signature Control

valve which operates on 6 volts. The AC adapter plugs
into the fireplace junction box A/C power supply. Four
(4) “AA” batteries are used for back up during power
outages.

2. The Signature Command System can also be operated

without A/C power. The system can run on four (4) “AA”
batteries for approximately six (6) months under normal
use.

3. A/C power must be used to power the A/C module,

blowers, lights and AUX accessories used with this
fireplace.

optional accessory requirements

1. This fireplace may be used with a wall switch and/or

Signature Command wireless controls.

2. The command center control may be mounted on the

wall with the use of the SCSWEK 15ft. wall mount exten-
sion kit.

w

arn

In

G

electrical connections should only
be performed by a qualified, licensed
electrician. Main power must be off when
connecting to main electrical power supply
or performing service. all wiring shall be
in compliance with all local, city and state
codes. the appliance, when installed, must
be electrically grounded in accordance with
local codes or in the absence of local codes,
with the national electrical code anSI/nFpa
70 (latest edition) and canadian electrical
code, cSa c22.1.

caut

Ion

Label all wires before disconnecting when
servicing controls. wiring errors can cause
improper and dangerous operation.

w

arn

In

G

Do not use open flame to check for gas
leaks.