Dryer Installation With Separate Exhaust (Preferred)

For ductwork less than 14 feet (5 m) and 2 elbows equivalent

and less than 0.3 inches (8 mm) static pressure:

NEVER exhaust the dryer into a chimney.

NEVER install wire mesh screen over the exhaust or

make-up air area.

NEVER exhaust into a wall, ceiling, or concealed space.

1.

Make-up air opening from outside the building may enter the

enclosure from the top or side walls. (See Dryer Make-Up Air

C h a r t )

2.

Enclosure (plenum) with service door. This separates the

dryer air from the room comfort air. If dryers use room air

instead of outside air, additional heat loss can be another

25 Btu/h (6.3 kcal/h) for each cubic foot per minute (cfm)

(.03m³/min.) used.

3.

Zero inches (mm) clearance to combustible material allowed on

sides and at points within 4 inches (102 mm) of front on top.

4.

Heat loss into laundry room from dryer front panels is about

60 Btu/h per square foot (15 kcal/h per 0.1m²).