Continuous Flow Icemaker Service Manual

Publication Number: 630460174SER

- 12 -

© 2004-2005, IMI Cornelius Inc.

REFRIGERATION SYSTEM

Thermostatic Expansion Valve NO Adjustment.

+/- 10 lbs. Discharge Pressure

Water Temperature

R

EFRIGERATION

S

YSTEM

A

DJUSTMENTS

A complete understanding of the icemaker and hermetic refrigeration system is necessary before any
adjustments are made. The refrigeration technician must use high and low side pressure readings, water
and air temperatures, plus general conditions of cleanliness to assess the refrigeration system status
when making any adjustments.

All icemaker products are tested and adjusted at the factory prior to shipment where the ambient
temperature ranges from 65° to 90°F, depending on the season of the year.

Whenever a new icemaker product is initially installed and started–up, it is imperative that the start–up
operation make the following checks and/or readjustments for local conditions.

E

XPANSION

V

ALVE

You will find a thermostatic expansion valve on icemakers, which is used to control the amount of
refrigerant flowing through the evaporator. Improperly installed or defective expansion valves may cause
low production, soft ice, squeaking from evaporator and excessive load inside evaporator.

By using general refrigeration system troubleshooting along with the pressure charts you can easily
determine whether or not the expansion valve is working properly.

A

DJUSTMENT

AND

T

ROUBLESHOOTING

When troubleshooting the expansion valve you must first be sure you have adequate water flowing into
evaporator, a clean condenser, unit is properly ventilated, and system is properly charged and free from
any restrictions. Also be sure compressor is operating properly.

Second, take reservoir water temperature and air temperature from condenser inlet and determine at
what pressure unit should be running. Machines are equipped with thermostatic valves, there is NO
adjustment. If correct pressure cannot be obtained, first be sure system has time to stabilize 10–15
minutes. Second, be sure sensing bulb is located at 12:00 position on outlet side of evaporator about 3–4
inches away from evaporator and be sure to insulate well and clamp tightly to tubing. If system pressures
are still not adequate, take a second water and air temperature reading and go over other parts of system
for possible problems. If proper charge is questionable evacuate and recharge to nameplate and leak
check. If valve still malfunctions replace valve.

When replacing valve be sure to bleed refrigerant gas from low side port so as not to lose refrigerant oil.
Use general refrigerant system practices when replacing and recharging unit. After new valve is in place,
go through previous monitored adjustments and troubleshooting to be sure valve is functioning properly.

NOTE: Units with thermostatic expansion valve—valve is located on bottom refrigerant line.
Sensing bulb is located on top refrigerant line. On water cooled units adjust condenser
modulating valve before troubleshooting expansion valve.

CAUTION: Very High discharge pressure is present in system. Quick disconnects on you gauges
will minimize danger and loss of refrigerant. Comply with federal regulations for reclaiming
refrigerant.

WCC 500

WCC 700

WCC 1000

WCC 2200

40°

65°

90°

50°

65°

90°

50°

65°

90°

50°

65°

90°

50°

162

166

168

60°

177

180

60°

171

172

60°

201

203

60°

188

‘92

194

70°

205

208

70°

199

200

70°

219

220

70°

214

218

220

80°

233

236

80°

227

228

80°

253

254

80°

245

249

251

90°

269

272

90°

263

264

90°

298

300

90°

275

279

281

100°

304

307

100°

298

299

100°

330

332

100°

309

313

315

328

334

340

324

328

332

362

364

366

Air T

e

mpera

tu

re